beautypg.com

Labeling the terminals, Removing the finger-safe terminal block – Rockwell Automation 1769-OF2 Compact (Series B or Later) Analog Output Module User Manual

Page 11

background image

Compact™ 1769-OF2 (Series B or Later) Analog Output Module 11

Publication 1769-IN049A-EN-P

(1) The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 120 mA per

1769-OF2 module minimum.

(2) Series B and later modules provide this option.

Labeling the Terminals

A removable, write-on label is provided with the module. Remove the label
from the door, mark the identification of each terminal with permanent ink,
and slide the label back into the door. Your markings (ID tag) will be
visible when the module door is closed.

Removing the Finger-Safe Terminal Block

To remove the terminal block, loosen the upper and lower retaining
screws. The terminal block will back away from the module as you remove
the screws. When replacing the terminal block, torque the retaining screws
to 0.46 Nm (4.1 in-lbs).

V out 0 +

I out 0 +

ANLG Com

NC

V out 1 +

I out 1 +

ANLG Com

NC

+24V dc

dc NEUT

+

-

Voltage Load

Current Load

earth ground

1769-OF2 Terminal Block

earth ground

External 24V dc Power

Supply

(1)

(optional)

(2)