Troubleshooting power ratings, P/s active – Rockwell Automation 1771-P7 AC (120/220V) 16A Power Supply Installation Instructions User Manual

Page 12

background image

P/S

Active

12627ĆI

I

O

AC (120/220V) 16A Power Supply

12

Publication 1771ĆIN056B EN-P - December 2001

Line 1

Line 2 or

neutral

Ground

Bus

ac power connectors

Grounding electrode

conductor

acpower

(customer

supplied)

À

A 3A 250V normalĆblow fuse protects the input line L1 from drawing more than 3 amperes.

14 AWG

L1

L2/N

GND

central ground bus (earth ground)

low side of the line power

high side of the line power

À

Connect

12626ĆI

I

O

The power supply has a green P/S ACTIVE LED that provides status
indication during power supply operation.

Normal operation

If indicator is Then

on

off

it may be due to:
input voltage not within specified range

blown fuse

overcurrent

Important: If a shutdown condition occurs, wait 15 seconds before

attempting to apply power.

For additional assistance, contact your local Allen-Bradley
representative.

Use these graphs to determine your:

cooling requirements

power cost

transformer size (unless the transformer manufacturer has a
recommended multiplier for sizing a transformer for an ac-to-dc
power supply)

0

4

8

12

16

20

60

100

140

180

0

4

8

12

16

0

30

60

90

120

Apparent Power (VA)

Real Power (Watts)

Backplane

Load Current

(Amps)

0

4

8

12

16

0

75

150

225

300

Transformer Sizing(VA) =

Real Power (Watts) x 2.5

Troubleshooting

Power Ratings