beautypg.com

Simplified schematic of pointblock – Rockwell Automation 1734D-IA16S PointBlock ac 16-Input Module Installation Notes User Manual

Page 2

background image

2 POINTBlock ac 16 Input Module

Publication 1734D-IN001A-EN-P - May 2001

Simplified Schematic of POINTBlock

ATTENTION

!

Whatever field power you supply is connected
to the internal field-power bus. For example, if
120V ac is applied to the power connections,
there will be 120V ac applied to the modules
through the internal field-power bus.

POINT I/O modules to the right of this module
will have this internal power bus voltage
applied, unless you use a 1734-FPD to interrupt
and change the field power-bus voltage.

CH

SH

24

CL

RT

En

CH

CL

GND

5V

DeviceNet
Connector

PointBus Expansion Port
(allows expansion of up to
12 POINT I/O modules)

Field Bus
Connector

24V
to 5V

Microprocessor

I/O Circuits

I/O Connections

Power
Connections

41971

120V ac