Wiring – Rockwell Automation 1793-IB16 Flex Integra Input Module Install Inst User Manual
Page 4
![background image](/manuals/579316/4/background.png)
4
FLEX Integra 16 Sink Input Module
Publication 1793-5.8 - December 1999
Wiring
This module is available with 2 styles of terminations: 1793-IB16 -
screw-cage and 1793-IB16S - spring-clamp. Refer to the wiring figure
below.
1.
Connect individual sensor signal input leads to terminals 0 through 15
on row A (channels 0 thru 15 respectively).
2.
Connect the associated sensor power lead to +24V dc on row (B).
3.
Connect +24V dc voltage to V terminal on row B.
4.
Connect 24V dc common to terminal COM on row A.
5.
If daisy-chaining + 24V dc from this module to the next Integra
module, connect a jumper from terminal V to terminal 8 on the next 8
point Integra module or terminal V on the next 16 point Integra
module.
6.
If daisy-chaining 24V dc common from this module to the next FLEX
Integra module, connect a jumper from terminal COM on this module
to terminal 0 on the next 8 point Integra module, or to terminal COM
on the next 16 point Integra module.
.
!
ATTENTION:
Total current draw through the module’s
(V) voltage terminals is limited to 10A. Separate power
connections to the module may be required.
A
B
0
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
COM
COM
V
V
41816
0
1
2 3
4
5
6
7
8
9 10 11 12 13 14 15
A
B
41814
V
V
COM
COM
1793-IB16
Where: COM = common, V = +24V dc power, 0 thru 15 = inputs
1793-IB16S