Choosing Module Features

Chapter 3

3Ć25

The transmission mode that you choose is determined by the
specifications of your ASCII device and the requirements of your
application (Table 2.L).

Table 2.L

Mode of Transmission

If Your

ASCII Device Is

And Your Application Requires

Then Select

Using Code

Full Duplex

That your ASCII device displays data sent to the ASCII module

That no data is displayed

Full Duplex with Echo

Full Duplex without

Echo

000

001

Simplex Read

Only the transmission of data from your ASCII device

Simplex Read or Full

Duplex

010

Simplex Write

Only the display of data received by your ASCII device

Simplex Write or Full

Duplex

011

Half Duplex

That your ASCII device displays data sent to the ASCII module

That no data is displayed

Half Duplex with Echo

Half Duplex without

Echo

100

101

Record the mode of transmission selection by writing the 3-digit code in
IW1(05-07). Use the form (found at the end of this chapter) or the boxes
below.

IW1

Mode

Transmission

07 06 05

Choose single transfer when you want the module to send a single string
to the processor in each block transfer, or when the string is long enough
to require more than one block transfer.

Choose multiple transfers when your ASCII device transmits short strings
(31 characters per string or less) at a high rate of transmission. Then the
module will include more than one string in each block transfer. The
highest number of strings that you can transfer in one block transfer is the
number of complete strings that the module can load into 62 (or fewer)
block transfer words.

Choosing Transmission Mode,

IW1(05Ć07)

Choosing Single or Multiple

Transfers, IW2(17)