beautypg.com

Ascii module plc-2 family processors appendix a – Rockwell Automation 1771-DA,D17716.5.13 U MNL 1771-DA ASCII I/O MODULE User Manual

Page 172

background image

ASCII Module

PLC-2 Family Processors

Appendix A

AĆ4

Figure A.2

Block Format Block Transfer Instructions

EN

BLOCK XFER READ

DATA ADDR:
MODULE ADDR:
BLOCK LENGTH:
FILE:

030
100

01

110 - 110

DN

010

07

110

07

EN

BLOCK XFER WRITE

DATA ADDR:
MODULE ADDR:
BLOCK LENGTH:
FILE:

030
100

01

110 - 110

DN

010

06

110

06

A block transfer instruction is programmed

in the ladder diagram by depressing the

[BLOCK XFER] key followed by [1] (for a

READ) or [0] (for a WRITE). The appropriate

read or write block, as shown, will

appear on the industrial terminal screen.

Numbers shown are default values.

Numbers in shaded areas must be

replaced by user-entered values. The

number of default address digits initially

displayed, 3, 4, or 5 will depend on the

size of the data table. Initially displayed

default values are governed by the I/O

rack configuration.

Data Address

: First possible address in accumulated value area of data table.

Module Address

: Rack, module group, and slot number.

Block Length

: Number of words to be transferred. (00 can be entered for default value or for 64 words).

File

:

Enable Bit (EN)

: Automatically entered from the module address. Set on when rung containing the instruction

Done Bit (DN)

: Automatically entered from the module address. Remains on for 1 scan following successful

is true.

transfer.

11121

Address of first word in the file. Storage is 100

8

above the data address.

Data and Module Addresses

The data address is the block transfer instruction address. It is used to
store the I/O rack address of the ASCII module (module address). The
module address is stored in BCD by rack, module group, and slot number
and identifies the module’s location in the I/O rack. You enter the data
address in the instruction after you enter the instruction.

The data address of a block transfer instruction should be the first
available address in the timer/counter accumulated area of the data table.
This address is 030 for the Mini-PLC-2/15 controller. For the PLC-2/30
controller, this address depends on the number of I/O racks connected to
the processor module, i.e. address 020 for one I/O rack, 030 for two racks,
etc. to 070 for six racks and 200 for seven racks. When more than one
block transfer module is used, the data addresses should be consecutive.