Environmental Specifications
Attribute
Value
Temperature,
operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
•
0…60 °C (32…140 °F)
Temperature, storage
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
•
-40…85 ° C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Un-packaged Damp Heat):
5…95% noncondensing
Vibration
IEC60068-2-6 (Test Fc, Operating): 2 g @ 10…500 Hz
Operating shock
IEC60068-2-27 (Test Ea, Unpackaged Shock): 30 g
Nonoperating shock
IEC60068-2-27 (Test Ea, Unpackaged Shock): 50 g
Emissions
CISPR 11: Group 1, Class A
ESD immunity
IEC 61000-4-2:
•
6 kV contact discharges
•
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
•
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
•
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
•
10V/m with 200 MHz 50% Pulse 100% AM @ 1890 MHz
•
1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4:
•
±4 kV @ 5 kHz on communication ports
Surge transient
immunity
IEC 61000-4-5:
±2 kV line-earth (CM) on communication ports
Conducted RF
immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Enclosure type rating