Rockwell Automation 1792-IB4/B INSTL.INST ARMORBLOCK 4 INPUT User Manual
Page 35
35
ArmorBlock 4 Input Module
Publication 1792-5.1 – October 1996
4 Input Module – Cat. No. 1792-IB4
General Specifications
DeviceNet Power
Voltage
Current
11.0 – 25.0V dc
100mA (no powered sensors)
300mA (full sensor load)
Surge Current at Power Up
Less than 10A for 5ms
Dimensions
Inches
Millimeters
2.6H X 7.7W X 3.06D
66H X 195W X 77.7D
Connectors
1792-IB4A/B – Aluminum connectors
1792-IB4S/B – Stainless Steel Connectors
Power Dissipation
Maximum
1.0 Watts
Thermal Dissipation Maximum
3.4 BTU/hr
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
–25 to 70
o
C (–13 to 158
o
F)
–40 to 85
o
C (–40 to 185
o
F)
up to 100%
30 g peak acceleration, 11(+1)ms pulse width
50 g peak acceleration, 11(+1)ms pulse width
Tested 10 g @ 10–500Hz per IEC 68-2-6
Conductors
Refer to publication 1485-6.7.1 for information
on cabling for your DeviceNet module.
Enclosure
Meets or exceeds NEMA 4X and 6P, IP67
1200psi, 140
o
F hosedown
Agency Certification
(when product or packaging is marked)
•
CSA certified
•
CSA Class I, Division 2, Groups A, B, C, D
certified
•
UL listed
•
CE marked for all applicable directives
This product has been tested at an Open DeviceNet Vendor Association,
Inc. (ODVA) authorized independent test laboratory and found to comply
with ODVA Conformance Test Software Version FT 1.2/1.0.