12 POINT I/O 8 Channel High Density Current Input Modules

Publication

1734-IN033B-EN-P - November 2010

Install a 1734-TOPS Base

1. Position the base vertically above the installed units, such as an

adapter, power supply, or existing module.

2. Slide the base down, allowing the interlocking side pieces to engage

the adjacent installed unit.

3. Press firmly to seat the base on the DIN rail until the base snaps into

place.

4. Verify that the DIN-rail locking screw is in a horizontal, locked

position before inserting an I/O module.

Remove a 1734-TOPS Base

To remove a wiring base from the DIN rail, you must remove the module
installed to the right of the base.

1. Squeeze the module locking mechanism of the module to the right of

the base, pulling up to remove the module.

2. Turn the orange locking screw to a vertical position to unlock the base

from the DIN rail.

3. Slide the base up to release it from its mating units.

Communicating with Your Module

I/O messages are sent to (consumed) and received from (produced) the
POINT I/O modules. These messages are mapped into the processor’s
memory. This POINT I/O input module produces 24 bytes of input data
(scanner Rx) and fault status data. It does not consume I/O data
(scanner Tx).