18 GuardPLC 1753-IF8XOF4 Analog I/O Module
Publication 1753-IN013A-EN-P - September 2005
Environmental Conditions
Storage Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
-40°C to +85°C (-40°F to +185°F) without backup battery
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0°C to +60°C (+32°F to +140°F)
Vibration
IEC60068-2-6 (Test Fc, Operating): 1 g @ 10…150 Hz
Shock, Operating
IEC60068-2-27 (Test Ea, Unpackaged Shock):15 g
Relative Humidity
IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
10 to 95% non-condensing
Emissions
Group 1, Class A
ESD Immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80% AM from 80 Hz to 2000 MHz
EFT/B Immunity
IEC 61000-4-4:
±2 kV @ 5 kHz on power ports
±1 kV @ 5 kHz on signal ports
±1 kV @ 5 kHz on communication ports
Surge Transient Immunity
IEC 61000-4-5:
±500V line-line (DM) and ±500 line-earth (CM) on DC power ports
±1 kV line-earth (CM) on shielded ports
±1 kV line-earth (CM) on communication ports
Conducted RF Immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz to 80 MHz
Enclosure Type Rating
meets IP20
Mechanical Dimensions
Width
207 mm (8.16 in.) including housing screws
Height
114 mm (4.49 in.) including latch
Depth
97 mm (3.82 in.) including grounding bolt
Weight
0.95 kg (2.09 lb)