Rockwell Automation 1794-ID2/B INSTALL INSTR 24v FLEX I/O 2 CHANNEL Incremental Encoder Module User Manual
Page 16
![background image](/manuals/579218/16/background.png)
16 FLEX I/O 2-Channel Incremental Encoder Module
Publication 1794-IN063C-EN-E - February 2014
Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…55 °C (32…131 °F)
Note: Do not connect maximum input voltage
simultaneously to all inputs if the module ambient
temperature is expected to exceed 40 °C.
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50 g
Emissions
CISPR 11 (IEC 61000-6-4): Class A
ESD immunity
IEC 61000-4-2:
4 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10 V/m with 1 kHz sine-wave 80%AM from
30 MHz…1000 MHz
EFT/B immunity
IEC 61000-4-4:
±2 kV @ 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5:
±2 kV line-earth(CM) on shielded ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from
150 kHz…80 MHz