Specifications – Rockwell Automation 1771-OQ16/C Isolated Output Module Installation Instr User Manual
Page 13
DC (24V) Isolated Output Module
13
Publication 1771ĆIN057B-EN-P - November 2002
Outputs per Module
16
Module Location
1771ĆA1B thru Ć A1B or later I/O Chassis
Voltage Rating
10 to 32V dc
Maximum Output Current
2.0A per output; 32.0A maximum per module at 0-45
o
C;
Derate linearly to 1.5A per output, 24A maximum per module at 60
o
C -
See derating curve.
Minimum Output Current
5mA
OnĆstate Voltage Drop (maximum) 0.34A per output at 2A
OffĆstate Leakage Current
(maximum)
0.5mA per output @ 32V dc, 25
o
C
Surge Current (maximum)
4A for 10ms per output., repeatable every 2 sec.
Power Rating
0.68W per output (maximum) @ 2A
Output Signal Delay Off to On
On to Off
100μs (max);
300μs (max)
Power Dissipation
13.0 Watts (max); 2.0 Watts (min)
Thermal Dissipation
44.3 BTU/hr (max); 6.8 BTU/hr (min)
Adjacent Slot Power Dissipation
10.0 Watts
Backplane Current
400mA maximum
Isolation Voltage
Testedfor 1s at 1500V channelĆtoĆchannel,
1500V channel to backplane
Maximum Cable Length
1000 ft (304.8 m)
Conductors Wire Size
Category
14 to 22 gauge (2.5mm
2
to 0.25mm
2
) strandedor solidcopper wire rated
at 60
o
C or greater
1, 2
3/64 inch insulation maximum
2
3
Environmental Conditions
Operating
Temperature
IEC 60068-2-1 (Test Ad, Operating Cold)
IEC 60068-2-2 (Test Bd, Operating Dry Heat)
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
32 to 140°F (0
o
to 60
o
C) See derating curve.
Storage Temperature
IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal Shock)
-40 to 185°F (-40 to 85
o
C)
Relative Humidity
IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat)
5 to 95%, noncondensing
Shock
Operating
Nonoperating
IEC 60068-2-27 (Test Ea, UnpackagedShock)
30g
50g
Vibration
IEC 60068-2-6 (Test Fc, Operating)
2g @ 10-500Hz
ESD Immunity
IEC 61000-4-2
4kV indirect discharges
Radiated RF Immunity
IEC 61000-4-3
10V/m, with 1kHz sine-wave 80% AM from 30MHz to 1000MHz
EFT/B Immunity
IEC 61000-4-4
+1kV @ 5kHz on signal ports
Surge Transient Immunity
IEC 61000-4-5
+1kV line-line (DM) and+2kV line-earth (CM) on signal ports
Specifications continued on next page.
Specifications