Rockwell Automation 1771-OQ16/C Isolated Output Module Installation Instr User Manual
Page 14

DC (24V) Isolated Output Module
14
Publication 1771ĆIN057B-EN-P - November 2002
Conducted RF Immunity
IEC 61000-4-6
10V rms with 1kHz sine wave 80% AM from 150kHz to 30MHz
Emissions
CISPR 11
Group 1, Class A (with appropriate enclosure)
Enclosure Type Rating
None (open-style)
Keying
Between 22 and24
Between 32 and34
Fuse
3A 2AG Fast Acting fuses (1 per output) Littelfuse P/N 225003
(Optional fuse kit Cat No. 1771ĆFF contains 5 fuses)
FieldWiring Arm
Catalog Number 1771ĆWN
Wiring Arm Screw Torque
7-9 pound-inches (0.8-1.0Nm)
Certifications
(when product is marked)
UL
UL ListedIndustrial Control Equipment
CSA
CSA CertifiedProcess Control Equipment
CSA
CSA CertifiedProcess Control Equipment for Class I,
Division 2 Group A, B, C, D Hazardous Locations
CE
4
European Union 89/336/EEC EMC Directive,
compliant with:
EN 50082-2, Industrial Immunity
EN 61236, Meas./Control/Lab., Industrial Requirements
EN 61000-6-2, Industrial Immunity
EN 61000-6-4, Industrial Emissions
C-Tick
4
Australian Radiocommunications Act, compliant with:
AS/NZS 2064, Industrial Emissions
1
One or two 14-22 AWG solidor strandedcopper wires per terminal. Must be same size. Do not intermix solidandstrandedwires.
Use copper wire only.
2
14AWG connectedto all terminals may not allow the fieldwiring arm cover to close. A smaller wire size may be required.
3
You use this conductor category information for planning conductor routing as described in publication 1770Ć4.1, Industrial
Automation Wiring and Grounding Guidelines.
4
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other certification details