Compact™ 240V ac Input Module

5

Publication 1769-IN011B-EN-P

Mounting Expansion I/O

Minimum Spacing

Maintain spacing from
enclosure walls,
wireways, adjacent
equipment, etc. Allow 50
mm (2 in.) of space on all
sides for adequate
ventilation, as shown:

Panel Mounting

Mount the module to a panel using two screws per module. Use M4 or #8
panhead screws. Mounting screws are required on every module.

Panel Mounting Using the Dimensional Template

!

ATTENTION: During panel or DIN rail mounting of all
devices, be sure that all debris (metal chips, wire strands, etc.) is
kept from falling into the module. Debris that falls into the
module could cause damage on power up.

Controller

Compact I/O

Compact I/O

Compact I/O

Compact I/O

Compact I/O

End Cap

Top

Bottom

Side

Side

Host Controller

Compact I/O

Compact I/O

Compact I/O

Right End Cap

NOTE: All dimensions
are in mm (inches). Hole
spacing tolerance:
±0.4 mm (0.016 in.)

For more than 2 modules: (number of modules - 1) X 35 mm (1.38 in.)

Refer to host controller documentation for this dimension.

132

(5.197)

122.6±0.2

(4.826±0.008)

35

(1.38)

28.5

(1.12)