Module Programming

Chapter 4

4–6

4.

Apply power to the I/O chassis. Enter the Block Transfer rung shown
in Figure 4.6 into the PLC–5/15 processor.

Figure 4.6

Block Transfer Rung for a PLC-5/15 Processor

NOTE: If the module is installed in a physical slot other than the fifth slot
to the right of the PLC processor, the BTR block will have to be set up
with a Rack/Group/Slot address other than 020. Refer to Figure

4.3

for the

correct address settings.

5.

Place the PLC–5/15 processor into RUN mode.

Use the Data Monitor in the 6200 Series Software to examine data table
address N36:0. This is where the processor has stored the rates and total
counts received from the 1771–QRD.

Only the channels which are actually driven will be active.