Rockwell Automation 1756-EN2T ControlLogix EtherNet/IP Module Installation Instructions User Manual
Page 23
ControlLogix EtherNet/IP Module 23
Rockwell Automation Publication 1756-IN603C-EN-P - April 2010
Environmental Specifications - 1756-EN2T
Attribute
1756-EN2T
Temperature, operating
• IEC 60068-2-1 (Test Ad, Operating
Cold)
• IEC 60068-2-2 (Test Bd, Operating Dry
Heat)
• IEC 60068-2-14 (Test Nb, Operating
Thermal Shock)
0…60 °C (32…140 °F)
Temperature, nonoperating
• EC 60068-2-1 (Test Ab, Unpackaged
Nonoperating Cold)
• IEC 60068-2-2 (Test Bb, Unpackaged
Nonoperating Dry Heat)
• IEC 60068-2-14 (Test Na, Unpackaged
Nonoperating Thermal Shock)
40…85 °C (-40…185 °F)
Relative humidity
• IEC 60068-2-30 (Test Db, Unpackaged
Damp Heat)
5…95% noncondensing
Vibration
• IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged
Shock)
30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged
Shock)
50 g
Emissions
• CISPR 11
Group 1, Class A
Immunity, ESD
• IEC 61000-4-2
6 kV contact discharges
8 kV air discharges
Immunity, radiated RF
• IEC 61000-4-3
10V/m with 1 kHz sine-wave 80%AM from
80…2000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 900
MHz
10V/m with 200 Hz 50% Pulse 100%AM at 1890
MHz
3V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz
Immunity, EFT/B
• IEC 61000-4-4
±2 kV at 5 kHz on Ethernet port
Immunity, surge transient
• IEC 61000-4-5
±2 kV line-earth(CM) on Ethernet port