beautypg.com

System planning – Rockwell Automation 1769-SDN Compact I/O DeviceNet Scanner Module Installation Instructions User Manual

Page 8

background image

8 Compact I/O DeviceNet Scanner Module

Publication 1769-IN060C-EN-P - May 2002

System Planning

Consider the following when planning your system:

The scanner can communicate with up to 63 DeviceNet devices.

The scanner, as a master, can own up to 63 slave I/O nodes.

The scanner can simultaneously be a master and be a slave owned by
another DeviceNet master.

A 1769-ECR (right end cap) or 1769-ECL (left end cap) is required to
terminate the end of the Compact I/O bus.

Each bank of Compact I/O must have its own power supply (a MicroLogix
1500 acts as the power supply for modules directly connected to it).

A Compact I/O power supply, or MicroLogix 1500 Base Unit, has limits in
the amount of +5V dc and +24V dc current it can supply to modules in its
I/O bank. These limits depend on the catalog number (e.g. 1769-PA2) of the
supply. A bank of modules must not exceed the current limits of the I/O
bank power supply or MicroLogix 1500 Base Unit.

Refer to the Compact 1769 Expansion I/O Power Supplies Installation
Instructions
, publication 1769-5.14 or the MicroLogix 1500 User Manual,
publication 1764-UM001A-EN-P.

The scanner has a distance rating of four, therefore the scanner must be
within four modules of the I/O bank’s power supply.

Determine the DeviceNet baud rate based on standard DeviceNet
considerations.

Consider the number of words of I/O data the host controller supports.

For more information on planning your DeviceNet network, refer to the DeviceNet
Cable System Planning and Installation Manual
, publication DN-6.7.2.