Installation Instructions

SLC

®

500 Programmable Controller Isolated

Link Coupler

(Catalog Number 1747-AIC)

Installing the DH-485
Communication Cable

Publication 1747-UM011, SLC 500 Modular Hardware Style User
Manual,
contains complete instructions and guidelines for DH-485
link planning.

Powering the Link Coupler

In normal operation with the programmable controller connected to
the link coupler, the processor powers both the link coupler and the
peripheral device (DTAM, PIC, HHT) — if connected — through the
1747-C11 cable. No external power supply is required.

If you do not connect the processor to the link coupler, use a Class 2
24V dc power supply to power the link coupler and peripheral
device.

USB (DF1)

RS485 (DH485)

RS232 (DH485)

USB to DH485

INTERFACE CONVERTER

USB

OK

SW

DH485

R

C

US

CAT

SER

FRN

1747-UIC

A

X.X

Mfg

XXXX

LISTED IND. CONT. EQ. FOR HAZ.

LOC. A196,

OPERATING TEMP CODE TAG

CLASS 1 GROUPS A, B, C, AND D, DIV. 2

MADE IN INDIA

N223

DH-485

Peripheral

CPU

Power

SLC 500

ALLEN-BRADLEY

1784-PCM4

Cable

SLC 500 Modular

Controller

to

1784-PCMK

card in

PCMCIA

slot

DH-485 Link

1747-AIC

Link Coupler

1747-C11

Cable

1747-PIC
Interface

Converter

SLC 500 Fixed

Controller

Use Belden#3106
or #9842 shielded,
twisted-pair cable.

Daisy-chain cable
segments together.

Total length of
cable segments
cannot exceed
1219m (4000 ft).

158 mm
(6.22 in)

1747-UIC
Interface
Converter

to USB port

Belden #3106A or #9642

to serial port

1747-C10

Cable

Personal

Computer

1747-C13

Cable

ATTENTION

!

Always connect the CHS GND (chassis ground)
terminal to the nearest earth ground. This connection
must be made whether or not an external 24V dc
power supply is used.