Catalog number explanation, Install the module, Set the node address – Rockwell Automation 1732D-IBDPM12MND DeviceNet ArmorBlock Network Powered 16-Input Module, Series A I.I. User Manual
Page 5
DeviceNet ArmorBlock™ Network Powered 16-input Module 5
Publication 1732D-IN007B-EN-E - November 2011
The DeviceNet network uses advanced network technology, producer/consumer
communication, to increase network functionality and throughput. Visit our web site
at
Catalog Number Explanation
The catalog number 1732D-IBDPM12MND refers to a DeviceNet 24V DC 8-port,
16-input mini-style network connector module.
Install the Module
To install the module:
•
Set the node address.
•
Mount the module.
•
Connect the cordsets.
Set the Node Address
Valid node addresses are 00…63.
Set the node address using either the rotary switches, RSNetWorx for DeviceNet,
DeviceNetManager, or another software configuration tool. Setting the switches at 64…99
lets the software have address control.
Each module is shipped with their node address set at 63. Remove the caps on the front of
the module to access the switches. The two switches are:
•
X10 (most significant digit) – left side of module
•
X1 (least significant digit) – right side of module
To reset the node address:
1. Rotate the switches using a small-bladed screwdriver.
2. Line up the small black dot on the switch with the number setting you wish
to use.
3. Cycle power.