![background image](/manuals/579068/2/background.png)
IMPORTANT: Apply grease to O-Ring
to retain into handle groove.
7-11 lb-in
1494F-M2 or -S2
2
Locating and Installing Door Catch
3
Installing Handle
C
B
Enclosure Door
Flange
Thickness
K
D
Enclosure
Base
22 - 37 lb-in
TOP VIEW
Door Catch
Mounting Bracket
Door Catch
Mounting Bracket
Door Catch
Door Catch
Top
1
3
Install GASKET
Install DEFEATER LEVER
PN-251880
DIR 10001103127 (Version 00)
Copyright © 2014 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
2
60-80 lb-in
Install SPRING BRACKET and HANDLE
SPRING BRACKET
7/16”
E
F
·
The Door Catch Mounting Bracket is provided with projections for welding. Projections can also be drilled out and then used as a guide
to locate hole centers in enclosure door.
·
User to supply the hardware for fastening the bracket.
·
Fasteners must provide the degree of ingress protection for the environmental rating of the enclosure.
·
The bracket hardware must be inaccessible to unauthorized personnel.
·
Dimension K (3/4" to 1")
·
When using large disconnect handle kit only (1494F-M2 or -S2), use Door Catch provided with handle kit.
·
When using large disconnect handle kit and small door hardware kits (1494V-L1, -LL1, -L2 or -LL2), use Door Catch provided with door
hardware kit.
·
Dimension K (1-1/8" to 1-3/8")
·
When using large disconnect handle kit only (1494F-M2 or -S2), use Door Catch (40492-080-02) which can be ordered from factory.
·
When using large disconnect handle kit and large door hardware kits (1494V-L3 or -LL3), use Door Catch provided with door hardware kit.
1/8” ALLEN
WRENCH
DEFEATER LEVER
SLOTTED