Example: decoupling of branches, Use in a tightly sealed enclosure – Rockwell Automation 1606-XLSRED Power Supply Reference Manual User Manual
Page 18
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
18
Rockwell Automation Publication 1606-RM009A-EN-P — February 2014
Bulletin 1606 Switched Mode Power Supplies
17.7. Example: Decoupling of Branches
Buffer energy supplied from a DC-UPS or buffer module is not wasted in “power branches.”
Please note:
Set output voltage of the power supply to a level that the buffer unit or DC-UPS will not start unexpected. Take the
voltage drop of the 1606-XLSRED into account.
Fig. 17-5 Wiring diagram, decoupling of buffered branches
Buffered
Load
e.g.
Controller
optional
I
I
I
L1
L2
PE
L3
Load
e.g. Motor
Buffer
Module
+
-
Failure
Monitor
1606-
XLSRED
Redundancy
Module
+
-
OUT
+
-
IN 1
+
-
IN 2
L1 L2 L3 PE
+ +
- -
1606-XLS480EA
Power
Supply
Adj
Overload
DCok
24V,20A
Note: Use separate mains systems for each power supply whenever it is possible
17.8. Use in a Tightly Sealed Enclosure
When the redundancy module is installed in a tightly sealed enclosure, the temperature inside the enclosure will be
higher than outside. The inside temperature defines the ambient temperature for the redundancy module.
Results from such an installation:
Power supply is placed in the middle of the box, no other heat producer is inside the box.
Enclosure:
Rittal Typ IP66 Box PK 9516 100, plastic, 110x180x165mm
Load:
24V, 16A; (=80%) load is placed outside the box
Input:
24Vdc
Temperature inside enclosure:
57.8°C (in the middle of the right side of the power supply with a distance of 2cm)
Temperature outside enclosure: 24.6°C
Temperature rise:
33.2K