beautypg.com

Example: decoupling of branches, Use in a tightly sealed enclosure – Rockwell Automation 1606-XLSRED Power Supply Reference Manual User Manual

Page 18

background image

All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

18

Rockwell Automation Publication 1606-RM009A-EN-P — February 2014

Bulletin 1606 Switched Mode Power Supplies

17.7. Example: Decoupling of Branches

Buffer energy supplied from a DC-UPS or buffer module is not wasted in “power branches.”

Please note:
Set output voltage of the power supply to a level that the buffer unit or DC-UPS will not start unexpected. Take the
voltage drop of the 1606-XLSRED into account.

Fig. 17-5 Wiring diagram, decoupling of buffered branches

Buffered

Load

e.g.

Controller

optional

I

I

I

L1
L2

PE

L3

Load

e.g. Motor

Buffer

Module

+

-

Failure

Monitor

1606-
XLSRED

Redundancy

Module

+

-

OUT

+

-

IN 1

+

-

IN 2

L1 L2 L3 PE

+ +

- -

1606-XLS480EA

Power

Supply

Adj

Overload

DCok

24V,20A

Note: Use separate mains systems for each power supply whenever it is possible

17.8. Use in a Tightly Sealed Enclosure

When the redundancy module is installed in a tightly sealed enclosure, the temperature inside the enclosure will be
higher than outside. The inside temperature defines the ambient temperature for the redundancy module.

Results from such an installation:

Power supply is placed in the middle of the box, no other heat producer is inside the box.

Enclosure:

Rittal Typ IP66 Box PK 9516 100, plastic, 110x180x165mm

Load:

24V, 16A; (=80%) load is placed outside the box

Input:

24Vdc

Temperature inside enclosure:

57.8°C (in the middle of the right side of the power supply with a distance of 2cm)

Temperature outside enclosure: 24.6°C
Temperature rise:

33.2K