Example: n+1 redundancy up to 30a, Example: battery back-up – Rockwell Automation 1606-XLSRED Power Supply Reference Manual User Manual
Page 16
![background image](/manuals/579060/16/background.png)
All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
16
Rockwell Automation Publication 1606-RM009A-EN-P — February 2014
Bulletin 1606 Switched Mode Power Supplies
17.4. Example: N+1 Redundancy up to 30A
N+1 Redundancy up to 30A requires four 10A power supplies and two 1606-XLSRED redundancy modules.
Fig. 17-2 Wiring diagram, n+1 Redundancy, 30A output current
optional
I
I
L
N
PE
I
1606-
XLSRED
Redundancy
Module
+
-
OUT
+
-
IN 1
+
-
IN 2
1606-
XLSRED
Redundancy
Module
+
-
OUT
+
-
IN 1
+
-
IN 2
L N PE
+ +
- -
Power
Supply
Adj
Overload
DCok
24V,10A
L N PE
+ +
- -
Power
Supply
Adj
Overload
DCok
24V,10A
L N PE
+ +
- -
1606-
XLS240EA
Power
Supply
Adj
Overload
DCok
24V,10A
Failure
Monitor
30A
Load
L N PE
+ +
- -
Power
Supply
Adj
Overload
DCok
24V,10A
I
Note: Use separate mains systems for each power supply whenever possible.
17.5. Example: Battery Back-up
A battery back-up with 10A requires one 10A power supply and one 1606-XLSRED redundancy module.
Please note:
Set output voltage of power supply to 26.5Vdc minimum to ensure that the load current is delivered from the power
supply and not from charger (battery). Use a fuse between battery and 1606-XLSRED.
Fig. 17-3 Wiring diagram, 10A Battery back-up
optional
L
N
PE
24V Battery
I
Battery
Charger
+
-
Failure
Monitor
10A
Load
L N PE
+ +
- -
1606-
XLS240EA
Power
Supply
Adj
Overload
DCok
24V,10A
1606-
XLSRED
Redundancy
Module
+
-
OUT
+
-
IN 1
+
-
IN 2
1606-
XLS240EA
1606-
XLS240EA
1606-
XLS240EA