Iv. conversion module specifications, Iii. compatibility – Rockwell Automation 1492-CM1771-LA004 Analog & Digital I/O Conversion Module User Manual
Page 4

(4)
IV. Conversion Module Specifications
(Operating specifications are when installed in the Conversion System base / cover-plate assembly)
III. Compatibility
1771
Analog I/O Module
1756
Analog I/O Module
1492
I/O Conversion Module
1492
Cable
1771-IL
1756-IF6I (6 ch Current)
1492-CM1771-LA004
1492-CONACAB005K
1771-IL
1756-IF6I (6 ch Current) (Qty 2)
1492-CM1771-LA004
1492-CONACAB005T1
1771-IL
1756-IF6I (6 ch Voltage) (Qty 2)
1492-CM1771-LA004
1492-CONACAB005T2
1771-IR
1756-IR6I
1492-CM1771-LA004
1492-CONACAB005F
1771-OQ (Qty 2) (Digital) 1756-OB16I
1492-CM1771-LA004
1492-C005005XT
1771-IL
1756-IF6I (6 ch Voltage)
1492-CM1771-LA004
1492-CONACAB005L
Foot Notes:
To understand any issues concerning I/O module compatibility, refer to the Installation Manuals for the specific
1771 and 1756 I/O modules involved.
The 3 numbers indicate the length of the 1492 Cable. Recommended cable lengths of 0.5M are shown.
Additional cable lengths are as follows:
1.0M = 1492-CONACAB010F or 1492-CONACAB010K or 1492-CONACAB010L
1.0M = 1492-CONACAB010T1 or 1492-CONACAB010T2
The 6 numbers indicate the cable length of each portion of the 1492 Cable. Recommended cable lengths of
0.5M / 0.5M are shown. Additional cable lengths are as follows:
1.0M / 1.0M = 1492-C010010XT
0.5M / 1.0M = 1492-C005010XT
1.0M / 0.5M = 1492-C010005XT
Specification
Value
Dimensions
Approximate Shipping Weight
Storage Temperature
-40 to +85 C (-40 to 185° F)
Operating Temperature
0 to 60 C (32 to 40° F)
Operating Humidity
5 to 95% at 60° C (non-condensing)
Shock
Non-operating
Operating
50g
30g
Operating Vibration
2g at 10 to 500Hz (Agrees with 1756 I/O module specification)
Maximum Operating Voltage
30
Vdc
Max. Module Operating Current
Per Point:
Per Module:
Agency Certifications
UL Classified: Under UL File Number E113724
CSA
CE: compliant for all applicable directives
Pollution Degree
2
Environmental Rating
IP20
Refer to the Wiring Diagram(s) for
current limits for a specific configuration.
NOTICE
2 Amps
12 Amps
11.81 in. (height) x 4.38 in. (depth) x 1.5 in. (width)
300 mm. (height) x 111.25 mm (depth) x 38.1 mm (width)
250.6 g (0.55 lbs) (includes carton)
PN-114290
DIR 10000060101 (Version 01)
Publication 1492-IN048B-EN-E