Installing Your 1394 DC Link Module

Dimensions

The 1394-DCLM dimensions are shown below.

Figure 1

1394-DCLM Dimensions

Mounting the 1394-DCLM

To mount the 1394-DCLM hardware:

1. Install the top mounting fastener on the system panel for the

1394-DCLM. The head of the fastener must be at least 6.35 mm
(0.25 in.) from the panel.

2. Hang the 1394-DCLM on the top mounting fastener.

Important: The 1394-DCLM must be the last (or right-most)

module in the 1394 system. This is the only module
that is ever mounted to the right of the 1394-DIM,
if used.
If the 1394-DCLM is used as a link between
two systems, the total wire distance between 1394-
DCLMs cannot exceed 3 meters (9.84 ft).

3. Engage the alignment tab so the 1394-DCLM is connected to the

module on its left.

Figure 2

Engaging the Alignment Tabs

350.0

(13.78)

400.0

(15.75)

50.0

(1.97)

25.0

(0.98)

Dimensions are in millimeters and (inches)

385.0 (fastener location)

1

(15.16)

8.0 (0.32)

All slots accept M6 or 1/4-20 mtg. screws

Mounting Hole Detail

12.0 (0.47)

8.0 (0.31)

8.0 (0.31)

10.1 (0.40)

15.9 (0.63)

1 Dimension shown is for mounting hardware
location and does not reflect the location
of the lower slot radius.

280

(11.02)

350

(13.78)

DC Link
Module

Engaged alignment tab