Dimensions, Mounting the 1394-dclm, The 1394-dclm dimensions are shown below – Rockwell Automation 1394-DCLM DC Link Module User Manual
Page 2
Publication 1394-5.11 December 1999
2
Installing Your 1394 DC Link Module
Dimensions
The 1394-DCLM dimensions are shown below.
Figure 1
1394-DCLM Dimensions
Mounting the 1394-DCLM
To mount the 1394-DCLM hardware:
1. Install the top mounting fastener on the system panel for the
1394-DCLM. The head of the fastener must be at least 6.35 mm
(0.25 in.) from the panel.
2. Hang the 1394-DCLM on the top mounting fastener.
Important: The 1394-DCLM must be the last (or right-most)
module in the 1394 system. This is the only module
that is ever mounted to the right of the 1394-DIM,
if used. If the 1394-DCLM is used as a link between
two systems, the total wire distance between 1394-
DCLMs cannot exceed 3 meters (9.84 ft).
3. Engage the alignment tab so the 1394-DCLM is connected to the
module on its left.
Figure 2
Engaging the Alignment Tabs
350.0
(13.78)
400.0
(15.75)
50.0
(1.97)
25.0
(0.98)
Dimensions are in millimeters and (inches)
385.0 (fastener location)
1
(15.16)
8.0 (0.32)
All slots accept M6 or 1/4-20 mtg. screws
Mounting Hole Detail
12.0 (0.47)
8.0 (0.31)
8.0 (0.31)
10.1 (0.40)
15.9 (0.63)
1 Dimension shown is for mounting hardware
location and does not reflect the location
of the lower slot radius.
280
(11.02)
350
(13.78)
DC Link
Module
Engaged alignment tab