Rockwell Automation 1492-CM1771-LD002 Field Wire Conversion Module User Manual
Page 4
V. 1492-CM1771-LD002 Conversion Module Specifications
(Operating specifications are when installed in the Conversion System base / cover-plate assembly)
VI. Appendix A - 1771 to 1756 Chassis Conversion System Selection Process
1) Determine the number of 1771 I/O modules used in the 1771 I/O Chassis to be converted to 1756. NOTE: In some
cases two 1756 modules may be required for one 1771 module. Select the applicable 1492 conversion modules from
the Digital and Analog Conversion Selection Table Matrix.
2) Review the Max Slots for I/O and chassis width data from the below table, and select a 1756 I/O Chassis which meets
your conversion needs from Step 1. Ensure the information from the I/O Conversion module tables are reviewed first.
3) Once the 1756 Chassis is selected, select the Conversion Assembly. The Conversion Assembly has the same dimen-
sional foot-print as the 1771 chassis and can use the same mounting hardware. The assembly consists of a base-plate
to hold the conversion modules and a cover-plate to protect the modules and to mount the selected 1756 chassis. The
combined depth of the conversion assembly with the 1756 chassis mounted is 10.25 inches (Controller w/key) to
10.0 inches (Controller w/o Key).
Foot Notes:
1771-A3B is not listed as it is used for 19 inch wide instrumentation panels
Two 1771 width dimensions are provided as some PLC-5 processors have integrated power supplies. Dimension w/PS
includes -P1, -P2, etc. Notice that the width dimension of some 1756 chassis exceed the width of the 1771 chassis with
or without the power supply. Cover-plate chassis mounting design allows the excess 1756 chassis width to be evenly
distributed to both sides, or excess to right or left. Carefully consider this in the conversion
1756-A4 may work in a 1771-A1B application if 4 or less I/O slots were used. Conversion cover-plate is capable to
mount -A4 or -A7
1756-A7 may work in a 1771-A2B application if 6 or less I/O slots were used. Conversion cover-plate is capable to
mount -A7 or -A10
1756-A10 may work in a 1771-A3B1 application if 10 or less I/O slots were used. Conversion cover-plate is capable to
mount -A10 or -A13
1756-A13 may work in a 1771-A4B application if 13 or less I/O slots were used. Conversion cover-plate is capable to
mount -A13 or -A17
PN-40373
DIR 10000060085 (Version 00)
Printed in U.S.A.
Max Slots for I/O
4
-A1B w/o
PS
4
-A1B
w/PS
3
6
8
8
6
9
12
-A13
(5)
12
-A3B1
-A10
-A7
(4)
-A2B
w/PS
-A2B w/o
PS
-A7
-A4
(3)
16
-A17
(6)
16
-A4B
Chassis Width
(2)
Conversion Assembly
Chassis Parameter
(1)
1756 Equivalent
Chassis
1756 Equivalent
Chassis
24.01
29.06
23.15
19.01
19.02
9.01
12.61
10.35
14.49
14.49
14.01
17.61
1771 Chassis
1771 Chassis
1771 Chassis
1492-MUA1B-A4-A7
1492-MUA2B-A7-A10
1492-MUA3-A10-A13
1492-MUA4-A13-A17
1771 Chassis
1756 Equivalent
Chassis
1756 Equivalent
Chassis
Specification
Dimensions
Approximate Shipping Weight
11.81 in. (height) x 4.38 in. (depth) x1.5 in. (width)
300 mm. (height) x 111.25 mm (depth) x 38.1 mm (width)
262.4 g (0.58 lbs) (includes carton)
Storage Temperature
-40 to +85°C (-40 to +185°F)
Operating Temperature
0 to 60°C (32 to 140°F)
Operating Humidity
5 to 95% at 60°C (non-condensing)
Shock
Non
-
operating
Operating
50g
30g
Operating Vibration
2g at 10 to 500Hz (Agrees with 1756 I/O module specifications)
Maximum Operating Voltage
240 Vac at 47 to 63Hz or 240 Vdc
Max. Module Operating Current
Per Point:
Per Module:
2 Amps
2 Amps
Agency Certifications
UL Classified: Under UL File Number E113724
CSA
CE: compliant for all applicable directives
Pollution Degree
2
Environmental Rating
IP20
Refer to the Wiring Diagram(s) for
current limits for a specific configuration.
NOTICE