Rockwell Automation 1492-CM1771-LD002 Field Wire Conversion Module User Manual
Rockwell Automation Equipment
Field Wire Conversion Module for A-B 1771-IAD to 1756-IH16I or 1771-IMD to 1756-IM16I
(Cat 1492-CM1771-LD002)
Local language (French, Italian, German & Spanish) versions of this document can be downloaded by going to www.ab.com.
In the left margin click on Publications Library and Literature Library. In the Search Area (right margin), Search by Catalog
Number and in the Search box type in the catalog number of the conversion system component.
I. Module Description
The 1492-CM1771-LD002 conversion module provides field wire signal conversion from an A-B 1771-IAD, 79 to
138Vac/dc, 16 point input module to a 1756-IH16I, 90 to 146Vdc , 16 point individually isolated input module or a
1771-IMD, 184 to 250Vac or 166 to 230Vdc, 16 point input module to a 1756-IM16I, 159 to 265Vac , 16 point
individually isolated input module. The conversion module provides the mating connector to the 1771-IAD or
1771-IMD module swing-arm/terminal block with the attached field wires. It routes those signals via its 37-pin
connector and a 1492-CONCAB Y pre-wired cable to compatible terminals on the 1756-IH16I or 1756-IM16I
(refer to Wiring Diagrams on page 2 and 3 for details).
II. Module Installation
The 1492-CM1771-LD002 conversion module must be installed in a 1492 conversion base-plate and cover-plate
assembly. The installation of the module into the assembly is explained in the Installation Manual that ships with the
conversion assembly. For a list of compatible assemblies refer to Appendix A.
III. Conversion Module Compatibility Matrix
This is cable length in meters. Available lengths are limited to 005 (0.5m) and 010 (1.0m).
Conversion Module
Compatible 1771
Input Module
Compatible 1756
Input Module
Required 1492 Cable
1492-CM1771-LD002
1771-IAD
1756-IH16I
1492-CONCAB Y
1492-CM1771-LD002
1771-IMD
1756-IM16I
1492-CONCAB Y
PN-40373
DIR 10000060085 (Version 00)
Printed in U.S.A.
1492-CM1771-LD002 Conversion Module
De-energize and lockout any and all power to all I/O field devices connected to the A-B 1771 I/O
Chassis, and the power to the 1771 I/O Chassis itself. Ensure all power is de-energized and locked out
to any device in the control cabinet where the conversion is to be performed. Ensure work is
performed by qualified personnel.
WARNING
Refer to conversion module Specifications Section: Maximum Operating Voltage
Conversion Compatibility and
Product I.D. Label
37-Pin Connector for cable 1492-CONCAB Y