Iii. compatibility, Iv. conversion module specifications – Rockwell Automation 1492-CM1771-LD0012 Field Wire Conversion Module User Manual
Page 3

(3)
Specification
Dimensions
Approximate Shipping Weight
11.81 in. (height) x 4.38 in. (depth) x 1.5 in. (width)
300 mm. (height) x 111.25 mm (depth) x 38.1 mm (width)
242.9 g (0.53 lbs) (includes carton)
Storage Temperature
-40 to +85°C (-40 to +185°F)
Operating Temperature
0 to 60°C (32 to 140°F)
Operating Humidity
5 to 95% at 60°C (non-condensing)
Shock
Non
-
operating
Operating
50g
30g
Operating Vibration
2g at 10 to 500Hz (Agrees with 1756 I/O module specifications)
Maximum Operating Voltage
132 Vac at 47 to 63Hz or 132 Vdc
Max. Module Operating Current
Per Point:
Per Module:
2 Amps
12 Amps
Agency Certifications
UL Classified: Under UL File Number E113724
CSA
CE: compliant for all applicable directives
Pollution Degree
2
Environmental Rating
IP20
Refer to the Wiring Diagram(s) for
current limits for a specific configuration.
NOTICE
Value
PN-114284
DIR 10000060095 (Version 01)
Publication 1492-IN042B-EN-E
1771
Digital I/O Module
1756
Digital I/O Module
1492
Conversion Module
1492
Cable
1771-OW
1756-OX8I
1492-CM1771-LD012
1492-CONCAB005Y
1771-OY
1756-OX8I
1492-CM1771-LD012
1492-CONCAB005Y
1771-OYL
1756-OX8I
1492-CM1771-LD012
1492-CONCAB005Y
1771-OZ
1756-OX8I
1492-CM1771-LD012
1492-CONCAB005Y
1771-OZL
1756-OX8I
1492-CM1771-LD012
1492-CONCAB005Y
1771-ID (Qty 2)
1756-IA16I
1492-CM1771-LD012 (Qty 2)
1492-C005005XL
1771-ID01 (Qty 2)
1756-IM16I
1492-CM1771-LD012 (Qty 2)
1492-C005005XL
1771-OD (Qty 2)
1756-OA16I
1492-CM1771-LD012 (Qty 2)
1492-C005005XM
1771-ODZ (Qty 2)
1756-OA16I
1492-CM1771-LD012 (Qty 2)
1492-C005005XP
1771-OR (Qty 2)
1756-OA16I
1492-CM1771-LD012 (Qty 2)
1492-C005005XR
III. Compatibility
Foot Notes:
To understand any issues concerning I/O module compatibility, refer to the Installation Manuals for the specific 1771
and 1756 I/O modules involved.
One conversion module required for each of the two 1771 nodules.
The 3 numbers indicate the cable length of the 1492 Cable. Recommended cable length of 0.5M is shown.
Additional
cable
lengths
are
as
follows:
1.0M = 1492-CONCAB010Y
The 6 numbers indicate the cable length of each portion of the 1492 Cable. Recommended cable lengths of 0.5M /
0.5M are shown. Additional cable lengths are as follows:
1.0M / 1.0M = 1492-C010010XL or 1492-C010010XM or 1492-C010010XP or 1492-C010010XR
0.5M / 1.0M = 1492-C005010XL or 1492-C005010XM or 1492-C005010XP or 1492-C005010XR
1.0M / 0.5M = 1492-C010005XL or 1492-C010005XM or 1492-C010005XP or 1492-C010005XR
Table 2: Bulletin 1771 to 1756 Conversion Modules and Cables
IV. Conversion Module Specifications
(Operating specifications are when installed in the Conversion System base / cover-plate assembly)