Rockwell Automation 1492-CM800-LD003 Field Wire Conv. Module for Modicon B805-016 or B853-016 to 1756-IA16 User Manual
Page 4

10000021858
(Version 00)
Printed in Germany
Article No. 4351860000
V. 1492-CM800-LD003 Conversion Module Specifications
(Operating specifications are when installed in the Conversion System base / cover-plate assembly)
VI. Appendix A - 800 Housing to 1756 Chassis Conversion System Selection Process
1) Determine the number of 800 I/O modules actually used in the 800 I/O Housing to be converted to 1756.
2) Review the data in Column 5 from the below table, and select a 1756 I/O Chassis which meets your conversion
needs from Step 1. Ensure the information from the I/O Conversion module table is reviewed first since in some
cases, two 1756 modules are needed to replace one 800 I/O module.
3) Once the 1756 Chassis is selected, refer to Column 7 and select the Conversion Assembly.
One chassis slot required for the ControlLogix processor or a remote I/O adapter type module.
The footprint and mounting dimensions of the 1492 Conversion Assembly (base plate and cover plate) match those of the Modicon
I/O Housing.
Width dimension includes the 1756 Chassis power supply.
Surplus Chassis width as compared to the 800 I/O Housing is divided equally when mounting it on the Conversion Assembly.
Mounting holes for the 1756 I/O Chassis are pre-drilled and pre-tapped into the Conversion Assembly cover plate.
Modicon is a Registered Trademark of Group Schneider.
Specification
Value
Dimensions
288.9 mm (height) x 139.7 mm (depth) x 44.5 mm (width)
11.37 in. (height) x 5.5 in. (depth) x 1.75 in. (width)
Approximate Shipping Weight
300g (0.66 lbs) (includes carton)
Storage Temperature
-40 to +85°C (-40 to +185°F)
Operating Temperature
0 to 55°C (32 to 131°F)
Operating Humidity
5 to 95% at 55°C (non-condensing)
Shock
Non-operating
Operating
50g
30g
Operating Vibration
2g @ 10-500Hz
Maximum Operating Voltage
125 Vac at 47 to 63 Hz
Max. Module Operating Current
Per Point:
Per Module:
2 Amps (1492-CABLE connection pins are limited to 2A per pin)
12 Amps
Agency Certifications
UL Classified: Under UL File Number E113724
CSA
CE: compliant for all applicable directives
Pollution Degree
2
Environmental Rating
IP20
AS-H810-xxx
AS-H819-103
AS-H819-209
AS-H819-100
AS-H827-103
AS-H827-209
AS-B827-100
Modicon 800 I/O
Housing Cat Number
1492-MUA4-MB3
1492-MUA7-A10-
MB4679
1492-MUA10-A13-
MB81011
Conversion Assembly
Catalog Number
3
4
6
7
8
10
11
10.25”
17.5”
17.5”
17.5”
27.1”
27.1”
27.1”
10.25”
A7 = 14.49”
A10 = 19.02”
A7 = 14.49”
A10 = 19.02”
A7 = 14.49”
A10 = 19.02”
A10 = 19.02”
A13 = 23.15”
A10 = 19.02”
A13 = 23.15”
A10 = 19.02”
A13 = 23.15”
1756 Chassis
Width
Dimension
3
A7 = 6, A10=9
A7 = 6, A10=9
A7 = 6, A10=9
A10 = 9, A13=12
A10 = 9, A13=12
A10 = 9, A13=12
1756 I/O Chassis
Catalog Number
1
7
2
3
6
5
4
1756-A4
1756-A7
or
1756-A10
1756-A10
or
1756-A13
Max. Number
of 800 Housing
Slots for I/O
800 Housing
Width
Dimension
Max. Number
of 1756 Chassis
Slots for I/O
Refer to the Wiring Diagram(s) for
current limits for a specific configuration.
NOTICE
1492-CM800-LD003 Conversion Module
De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O
housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out
to any device in the control cabinet where the conversion is to be performed. Ensure work is
performed by qualified personnel.
WARNING
Refer to conversion module Specifications Section: Maximum Operating Voltage
10
L2-0
IN-0
1
IN-1
2
IN-2
3
IN-3
4
IN-4
5
IN-5
6
IN-6
7
IN-7
8
IN-8
11
IN-9
12
IN-10
13
IN-11
14
IN-12
15
IN-13
16
IN-14
17
IN-15
18
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
L2-1
20
9
L2-0
19
L2-1
9
1
1
19
2
3
3
4
4
5
5
6
6
7
7
8
8
9
19
10
11
11
12
12
13
13
14
15
15
16
16
17
17
18
18
20
14
2
L1
L2
Input 13
Input 15
Input 14
Input 16
Input 5
Input 7
Input 6
Input 8
Input 1
Input 3
Input 2
Input 4
Input 9
Input 11
Input 10
Input 12
Neutral Grp 1
Neutral Grp 2
10
20
Not Used
Not Used