Battery modules, Description, Specification quick reference – Rockwell Automation 1606-XLSBATBR1 Power Supply Reference Manual User Manual
Page 2: Catalog numbers, Certification marks

All parameters are specified at 25°C ambient unless noted otherwise.
2
Rockwell Automation Publication 1606-RM037A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
Battery Modules
A modular concept allows the user to meet individual
application demands and is available with two different
options:
You can order the module with an assembled battery or
you can choose only the bracket allowing the mounting
of individual batteries – such a long life or higher current
which achieves a longer buffer-time. The mounting
bracket allows you to assemble the battery just in time,
thus avoiding outdated batteries due to limited shelf life.
Two mounting options:
DIN rail or panel/wall mounting
Easy access to the terminals and the fuse
Heavy duty fuse holder and spare fuse included
Description
Specification Quick Reference
Battery
Maintenance free valve regulated lead acid battery
Battery voltage nom 12Vdc
Battery capacity nom 7Ah
Self-discharge typ
3%/ month at 20°C
Design life (EUROBAT) 3 to 5 years
Fuse
Blade terminal fuse
nom
30A ATO
®
)
e
s
u
f
l
e
t
t
i
L
0
3
0
7
5
2
(
Terminals and Wiring
Type Screw terminals
Solid wire nom 2.5-4mm
2
Stranded wire nom 2.5-4mm
2
American wire gauge
max 12 AWG
Wire stripping length
nom 7mm / 0.275”
Tightening torque nom 0.8Nm / 7lb.in
Ambient Temperature
Operation min +0°C to +40°C
Storage and transport
min -20°C to +50°C
Instructions for Use and Disposal of the Battery
Place the battery module outside the cabinet or in the
coolest area when used inside the cabinet.
Use wires no smaller than 2.5mm
2
(or 12 AWG) and no
longer than 2x1.5m (cord length 1.5m).
Disconnect battery fuse before working on the battery
or on the DC-UPS.
To replace battery, loosen screw with only one turn and
slide the mounting bracket up.
For storage, installation and operation, the
requirements of the EN 50272-2 as well as other
national regulations must be observed.
Ensure sufficient ventilation for the battery.
Always dispose the batteries through a recycling
organisation. Batteries must be completely discharged
before recycling.
Dimensions and Weight (1606-XLSBATASSY1)
Widtt nom 155mm / 6.1“
Height nom 124mm / 4.88“
Depth nom 112mm / 4.41“
Weight max 3200g / 7.06lb
The DIN rail height when used must be added to the depth
to calculate the total required installation unit depth.
Warranty
3 Year limited warranty except battery as battery is
considered as a service part. Special conditions are part of
our general terms and conditions. Do not store the battery
longer than 9 month without supplementary charge or
performance might change.
Catalog Numbers
Certification Marks
1606-XLSBATASSY
Battery module with battery
1606-XLSBATBR1
Mounting kit without battery
1606-XLSBAT1
Battery replacement
GL
Marine
Battery, terminal block,
cables, fuse and fuse
holder are UL-approved
components.
GOST R