Rockwell Automation 1000-SB012 Solar Combination Enclosure User Manual
Page 6
Rockwell Automation Publication 1000-IN002B-EN-P - April 2012
6 Solar Combiner Enclosure
2.
Use a hole cutter or hole saw to create holes at the top and bottom of the
enclosure.
Install the Conduit Connector and Grounding Adapter
Install the conduit connector (hub) and grounding adapter by following these
steps.
1.
Place the conduit connector (hub) and O-ring onto the conduit in the
desired locations.
2.
Secure the conduit connector to the enclosure by using the locknut.
3.
Install the grounding adapter as shown in
Figure 2
and secure with the
locknut.
Figure 2 - Connector and Adapter Installation
TIP
When using a hole cutter, place the punch on the inside of the enclosure and
draw it through to the outside.
IMPORTANT
To guard against enclosure damage, align the conduit to prevent unnecessary stress on
the enclosure walls.
IMPORTANT
For conduit hubs, use only raintight or wet-location hubs that comply with the
requirements in the UL514B standard for Fittings for Conduit and Outlet Boxes.
TIP
Make sure that the wiring terminal is positioned so that it will be accessible
after installation.
Conduit
Conduit
Connector (hub)
O-ring
(outside enclosure)
Enclosure
Hole Size
Locknut
Positioning Tab
Wiring Terminal
Grounding Adapter
Locknut