Wiring – Rockwell Automation 1204 Reflected Wave Reduction Device User Manual

Page 7

background image

1204 Reflected Wave Reduction Device with Common Mode Choke

7

Wiring

4. Wire the device as indicated below. The maximum and minimum wire

size accepted by the RWC terminal block is 4.0 and 0.75 mm

2

(10 and

18 AWG). Use copper wire only with a minimum temperature rating of
75 degrees C. Maximum torque is 1.81 N-m (16 lb.-in.).

Motor Phase U

RWC Terminal Block

AC Drive

Motor Phase V

Motor Phase W

Motor Ground

from Drive Terminal W

from Drive Terminal V

from Drive Terminal U

from Drive Ground

U

V

W

PE

PE

U1

V1

W1

3.1 m (10 ft.) - Maximum Length

(

)

g