25.12. Mounting Orientations

Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).

Fig. 25-5

Mounting
Orientation A
(Standard
orientation)

Power

Supply

OUTPUT

INPUT

Output Power

0

10

20

30

40

60°C

12

36

48

60W

50

A1

24

Ambient Temperature

Fig. 25-6

Mounting
Orientation B
(Upside down)

Power

Supply

OUTPU

T

INPUT

Output Power

0

10

20

30

40

60°C

12

36

48

60W

50

24

A1

A2

Ambient Temperature

Fig. 25-7

Mounting
Orientation C
(Table-top
mounting)

Output Power

0

10

20

30

40

60°C

12

36

48

60W

50

24

A1

A2

Ambient Temperature

Fig. 25-8

Mounting
Orientation D
(Horizontal cw)

Power

Supply

OUTPUT

INPUT

Output Power

0

10

20

30

40

60°C

12

36

48

60W

50

24

A1

A2

Ambient Temperature

Fig. 25-9

Mounting
Orientation E
(Horizontal ccw)

Power Supply

OUTPUT

IN

PUT

Output Power

0

10

20

30

40

60°C

12

36

48

60W

50

24

A1

A2

Ambient Temperature