Physical dimensions and weight, Installation and operating instructions – Rockwell Automation 1606-XLE960MX-3N Power Supply Reference Manual User Manual
Page 15
All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM025A-EN-P — April 2014
15
Bulletin 1606 Switched Mode Power Supplies
21. Physical Dimensions and Weight
Weight
1400g / 3.09lb
DIN Rail
Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
The DIN rail height must be added to the depth (157mm) to calculate the total required
installation depth.
Fig. 21-1 Front view
Fig. 21-2 Side view
22. Installation and Operating Instructions
Mounting and installation:
Output terminal must be located on top and input terminal on the bottom. For other orientations, see section 25.12.
An appropriate electrical and fire end-product enclosure needs to be configured in the end-use application.
Cooling:
Convection cooled, no forced air cooling required. Do not block ventilation grille by more than 30%!
Installation clearances:
40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently
with full power. If the adjacent device is a heat source, 15mm clearance is recommended.
Risk of electrical shock, fire, personal injury or death!
Do not use the unit without proper earth connection (Protective Earth). Use the pin on the terminal block for earth
connection and not one of the screws on the housing.
Turn power off before working on the power supply. Protect against inadvertent re-powering.
Make sure the wiring is correct by following all local and national codes.
Do not open, modify or repair the unit.
Use caution to prevent any foreign object from entering the housing.
Do not use in wet locations or in areas where moisture and/or condensation are likely to occur.
Service parts:
The unit does not contain any field replaceable part. In case of damage or malfunction, turn power off immediately
and return the unit to the manufacturer for inspection.