1397 Enhanced Field Supply Card

8

1397-5.24 March, 2005

— Front —

100-150

HP/230V Drives

200-300

HP/460V Drives

— Inside Right Side Panel —

400-600

HP/460V Drives

— Top —

40-75

HP/230V Drives

75-150

HP/460V Drives

— Top —

1.5-30

HP/230V Drives

3-60

HP/460V Drives

TORQUE

14-10GA 35 LB.-IN.

0 GA 48 LB.-IN.

SPEC

GND

DANGER

CIRCUIT BREAKER DOES NOT DISCONNECT INCOMING A0
LINE POWER IT ONLY PROVIDES DC FAULT PROTECTION.

LE DISCONECTEUR NE COUPTE PAS L'AUTOMENTATION DU SPOTEUR IL NES
SERT QUE A ASSURER UNE PROTECTION CONTRE LES DESFAULTS DC.

810903-2424

!

DANGER

RISK OF ELECTRICAL SHOCK. DISCONNECT INPUT
POWER BEFORE SERVICING EQUIPMENT.

P/N 33145

6FU 7FU 8FU

6FU 7FU 8FU

6FU 7FU 8FU

A

B

C

581

583

582

X1

X2

H1

H2

F2/35

CT

LINE

F1/37

9

Replace fuses 6FU, 7FU

&

8FU with the (3) UL class

CC/600V/25A fuses included with the kit.
Locate the replacement fuse table on the back of the carrier.
Attach one of the adhesive fuse rating labels (P/N 179540) over
the 600V 15A designations as shown in the illustration.

Installation, Cont’d