1336 PLUS II Firmware Download Module
18.If errors occurred in the transfer, the screen may display one of the
following:
•
Error in Constant Block
•
Error in Program Block
•
Error in DSP Block
•
Error in Text and Language Block
If errors are indicated, press the Enter key on the computer and return to
step 10 on page 4 to repeat the entire process from that point.
19.If no errors have occurred . . .
A. Remove all power from the drive and wait at least 60 seconds for the
bus to discharge.
B. Remove the communications cable from the module and computer.
Remove the Firmware Download Module by grasping the 4 locking
tabs, then squeeze the tabs and pull the module towards you.
C. Reinstall the HIM or communications option and the Control
Interface Board, if previously removed.
D. Apply power to the drive and wait 60 seconds. If J14 is not installed, a
DSP Protected fault (F46) will occur on power-up.
E. When the Stop LED illuminates, remove drive power.
F. Remove jumpers J14 and J20. Store jumpers in a spare location.
G. Use a felt tip pen to mark the new Software Revision number on the
Main Control Board label.
H. Apply power to the drive. One of the following conditions should
occur:
20.Download is complete! Reprogram the drive parameters and place this
document with your User Manual for future reference.
Condition
Action
then . . .
Drive active. No faults.
If J14 is installed
Power down and remove J14. Procedure is complete
If J14 is Not installed
Procedure is complete
EE Init or other EE fault
occurs
Use the HIM EEPROM Menu
to reset the drive to factory
defaults
If J14 is installed
Power down and remove J14.
Procedure is complete
if J14 is Not installed
Procedure is complete
DSP Protected (F46) fault
Install jumper J14
Cycle power a second time. Power down and remove J14.
Process complete
HIM Continuously displays
“Connecting….Connecting….
Repeat entire procedure