Purpose
This publication will guide you through installation of the Control
Interface Option board (L4, L4E, L5, L5E, L6, L6E). Refer to the 1336
PLUS User Manual (publication 1336 PLUS-5.0) for further information
on wiring and operation.
ATTENTION: This drive contains ESD (Electrostatic
Discharge) sensitive parts and assemblies. Static control precau-
tions are required when installing, testing, servicing or repairing
this assembly. Component damage may result if ESD control
procedures are not followed. If you are not familiar with static
control procedures, reference A-B publication 8000-4.5.2,
“Guarding Against Electrostatic Damage” or any other applica-
ble ESD protection handbook.
ATTENTION: To avoid a shock hazard, assure that all power to
the drive has been removed before proceeding with the follow-
ing procedure. In addition, verify that the DC bus has discharged
by measuring across the “+ DC” and “– DC” terminals of TB1
with a voltmeter. The voltage should be 0.0V DC.
Remove and lock-out all incoming power to the drive. Remove the drive
cover.
❏ 1. Locate and remove the two Main Control Board jumpers installed at
pins 3 & 4 and 17 & 18 of J4 on 0.37-3.7 kW (0.5-5 HP) drives or J7
on 5.5-45 kW (7.5-60 HP) drives. See figure on reverse side.
Important: Retain the jumpers just removed. If the Control
Interface Board is removed at a later time these jumpers must be
reinstalled. In addition, the [Input Mode] parameter will have to be
programmed to “1.”
❏ 2. Position the Control Interface Board over the 2 connectors on the
Main Control Board, observing correct orientation (see figure).
ALLEN-BRADLEY
1336 PLUS Control Interface
Option Installation
(L4, L4E, L5, L5E, L6, L6E)
Instructions
!
!
Interface Board Installation