beautypg.com

Wiring specifications – Rockwell Automation 1397 Pulse Encoder Interface Installation Inst. User Manual

Page 8

background image

1397 Pulse Encoder Interface Card

8

1397-5.13 June, 1997

Shield

1

to Chassis

Ground Stud

71 +15V

72 COM

73 A

74 A

Single Channel

Pulse Encoder

— No Motor Reversing —

75 B

76 B

TB J6

TB J5

A

(High)

(Low)

(High)

(Low)

A

Period

2

1

Belden 9728 or 9730 — (2) Conductor Twisted Shielded Cable

Refer to the Cable and Wire Recommendations in the 1397 Use

Manual for additional Wiring Specifications

2

Period = 1

frequency

Non-Regenerative Drives — Non-Reversing Motor Applications

Shield

1

to Chassis

Ground Stud

71 +15V

72 COM

73 A

74 A

Quadrature

(Dual-Channel)

Pulse Encoder

for

Regenerative Drives

75 B

76 B

TB J6

TB J5

B

A

(High)

(High)

(High)

(Low)

(Low)

(Low)

(High)

(Low)

A

B

Period

2

1

Belden 9728 or 9730 — (2) conductor twisted shielded cable.

Refer to the Cable and Wire Recommendations in the 1397

User Manual for additional wiring specifications.

2

Period = 1

frequency

Regenerative Drives — Reversing and Non-Regenerative Motor Applications

Wiring Specifications

Terminal Blocks J5 and J6 are available for either regenerative or
non-regenerative drive connection.

Note: Only regenerative drives allow motor reversing. Regenerative

drives require that quadrature pulse encoders be used.

ATTENTION: The incorrect wiring of the pulse encoder
and/or motor can cause an overspeed condition. Verify
correct motor and pulse encoder polarity in the Start-Up and
Adjustment section of the 1397 User Manual. Failure to
observe this precaution could result in bodily injury.

!