Iii. compatiblity, Iv. conversion module specifications – Rockwell Automation 1492-CM1771-LD001 Digital I/O Conversion Module User Manual
Page 3
(3)
III. Compatiblity
Foot Notes:
To understand any issues concerning I/O module compatibility, refer to the Installation Manuals for the specific
1771 and 1756 I/O modules involved.
The 3 numbers indicate the cable length of each portion of the 1492 Cable. Recommended cable lengths of 0.5M
are shown. Additional cable lengths are as follows:
1.0M = 1492-CONCAB010X
PN-114270
DIR 10000060084 (Version 01)
Publication 1492-IN035B-EN-E
IV. Conversion Module Specifications
(Operating specifications are when installed in the Conversion System base / cover-plate assembly)
Specification
Dimensions
Approximate Shipping Weight
11.81 in. (height) x 4.38 in. (depth) x 1.5 in. (width)
300 mm. (height) x 111.25 mm (depth) x 38.1 mm (width)
258.3 g (0.59 lbs) (includes carton)
Storage Temperature
-40 to +85°C (-40 to +185°F)
Operating Temperature
0 to 60°C (32 to 140°F)
Operating Humidity
5 to 95% at 60°C (non-condensing)
Shock
Non
-
operating
Operating
50g
30g
Operating Vibration
2g at 10 to 500Hz (Agrees with 1756 I/O module specifications)
Maximum Operating Voltage
132 Vac at 47 to 63Hz or 132 Vdc
Max. Module Operating Current
Per Point:
Per Module:
2 Amps
2 Amps
Agency Certifications
UL Classified: Under UL File Number E113724
CSA
CE: compliant for all applicable directives
Pollution Degree
2
Environmental Rating
IP20
Refer to the Wiring Diagram(s) for
current limits for a specific configuration.
NOTICE
Table 2: Bulletin 1771 to 1756 Conversion Modules and Cables
1771
Digital I/O Module
1756
Digital I/O Module
1492
Conversion Module
1492
Cable
1771-IAD 1756-IA16 1492-CM1771-LD001
1492-CONCAB005X
1771-IBD 1756-IB16 1492-CM1771-LD001
1492-CONCAB005X
1771-ICD 1756-IC16 1492-CM1771-LD001
1492-CONCAB005X
1771-IND 1756-IN16 1492-CM1771-LD001
1492-CONCAB005X
1771-IND1 1756-IN16 1492-CM1771-LD001
1492-CONCAB005X