beautypg.com

Daisy chaining outputs, Inductive and capacitive loads – Rockwell Automation 1606-XLP60BQT Power Supply Reference Manual User Manual

Page 19

background image

All parameters are specified at 12V, 4.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM016A-EN-P — February 2014

19

Bulletin 1606 Switched Mode Power Supplies

20.6. Daisy Chaining Outputs

Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current
through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block.

Fig. 20-3 Daisy chaining of outputs

Fig. 20-4 Using distribution terminals

Power

Supply

+ +

- -

Input

Output

Load

+

-

max 25A!

Power

Supply

+ +

- -

Input

Output

Load

+

-

Distribution

Terminals

Power

Supply

+ +

- -

Input

Output

Power

Supply

+ +

- -

Input

Output

20.7. Inductive and Capacitive Loads

The unit is designed to supply any type of load, including unlimited capacitive and inductive loads.