Rockwell Automation 1485 PowerTap Connection User Manual
Rockwell Automation Equipment
Installation Instructions
Bulletin 1485 PowerTap
Connection
IMPORTANT: Power: 15.0 Amps maximum total current; 7.5 Amps each trunk at 25
°
C (1485T–P2T5–T5).
Power: 6.0 Amps maximum total current; 3.0 Amps each trunk at 25
°
C (1485T–P2T5–T5C).
ATTENTION: Under some conditions of load
current and ambient temperature the fuse current
value should be decreased. As shipped, the
1485T–P2T5–T5 PowerTap connection is fused to
supply up to 7.5 Amps to one trunk line, the
1485T–P2T5–T5C 3.0 Amps.
Description
For power requirements on your DeviceNet
network,
Allen-Bradley is introducing its PowerTap connection. The
PowerTap connection is a passive coupling device used to
limit trunk current and is also used to permit the connection of
multiple power supplies to the trunk without mutual
interference.
Figure 1: PowerTap Connection
Part Number: 1485T–P2T5–T5 and 1485T–P2T5–T5C
Dimensions—mm (inches)
Specifications
Storage Temperature
-40
°
C to +85
°
C (-40
°
F to 185
°
F)
Operating Temperature
-25
°
C to +70
°
C max
Operating Humidity
5%-95% relative (noncondensing)
Washdown Rating
1200 PSI (8270kPa) @ 60_C (140_F)
Washdown Rating
1200 PSI (8270kPa) @ 60 C (140 F)
NEMA 3, 4x, 6P, 12 and 13
Housing Material
Black polyester
Note: In class II applications the fuses are used as a means for
isolating network segments. For more information refer to DeviceNet
Cable Installation Guide.
Enclosure
111.25
(4.38)
98.04
(3.86)
67
(2.63)
98
(3.87)
Trunk Connection
Terminals
DC Power Supply
Connection Terminals
6.6
(0.26)
1485T-P2T5-T5-T5: Colors PG16 Cable Grips
1485T-P2T5-T5C-T5C: Colors PG9 Cable Grips
Figure 2: Wiring Diagram
1485T–P2T5–T5:
Power Requirements: 24V DC
1
% @
15.0 Amp (maximum)
7.5 Amp Fast Blow Automotive Type
Fuse in each Trunk +24V DC Leg
(Littlefuse model 297 07.5 or similar)
1485T–P2T5–T5C:
Power Requirements: 24V DC
1
% @
6.0 Amp (maximum)
3.0 Amp Fast Blow Automotive Type
Fuse in each Trunk +24V DC Leg
(Littlefuse model 297 03 or similar)
Note:
Red
+24V
White CAN Hi
Blue
CAN Lo
Black
Common
Terminal Block for
PCB
Black Blue Drain White Red
Red White Drain Blue Black
Red
Black
Drain
Power Supply Connection
Terminal Block for
Trunk Connections
1485T-P2T5-T5 Mini Type Fuse, 7.5A Max.
1485T-P2T5-T5C Mini Type Fuse, 3.0A Max.