Floor mounting, Figure 1 - bottom view floor mount dimensions, Clearance – Rockwell Automation 1608P ProDySC User Manual, 200 A User Manual
Page 8: Bypass switch, Circuit breaker recommendations, Table 1 - recommended branch circuit protection

8
Rockwell Automation Publication 1608P-UM003A-EN-P - September 2013
Chapter 2
Installation
Floor Mounting
The ProDySC is to be secured to the floor using fasteners and fittings appropriate
for the type of floor. Holes are provided in the base channels; see
for
mounting dimensions.
Note: Top or bottom cable entry is allowed. See
.
Figure 1 - Bottom View Floor Mount Dimensions
Clearance
ProDySC doors hinge on both right and left. See
for
dimensions including door swing. Leave required clearances:
•
Door swing must allow doors to open at least 90 degrees
•
12” [300mm] clearance on left side and rear for cooling airflow
•
4”[100mm] on right side for air filter clearance when right door opens
Bypass Switch
Installation of an external maintenance bypass switch is recommended for service
and/or maintenance. Typical switch arrangements are shown in
and
. Contact Rockwell Automation for
recommendations and requirements.
Circuit Breaker
Recommendations
Branch circuit protection upstream of the ProDySC is required. Recommended
circuit breakers and maximum allowed circuit breaker ratings are listed in
. Branch circuit protection rated less than the ProDySC current rating
may result in nuisance tripping.
Table 1 - Recommended Branch Circuit Protection
ProDySC Rating
Max. MCCB Rating
200 A
250 A