Use one of the following cable types to connect the UPS to the EPO switch:
•
CL2: Class 2 cable for general use
•
CL2P: Plenum cable for use in ducts, plenums, and other sp aces used for environmental air.
•
CL2R: Riser cable for use in a vertical run in a floor to floor shaft.
•
CLEX: Limited use cable for use in dwellings and for use in raceways.
•
For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable).
Terminal Mode to Configure UPS Parameters
Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS.
Connect the serial cable to the serial com connector on the back of the UPS.
1609-P5000E models only: Remove the 1609-NMC network management card from the slot located
in the rear of the unit.
1. EXIT the PowerChute Business Edition using the following steps:
•
From the Desktop, go to Start => Settings => Control Panel => Administrative Tools =>
Services.
•
Select APC PCBE Server and APC PCBE Agent – right click the mouse and select Stop.
2. Open a terminal program. Example: HyperTerminal
•
From the Desktop, go to Start => Programs => Accessories => Communication
=>HyperTerminal.
3. Double-click on the HyperTerminal icon.
•
Follow the prompts to choose a name and select an icon. Disregard the message, “...must
install a modem,” if it is displayed. Click OK.
•
Select the COM port that is connected to your UPS. The port settings are:
ü
bits per second - 2400
ü
data - bits 8
ü
parity - none
ü
stop bit - 1
ü
flow control - none
•
Press ENTER
4. Example for setting the number of external battery packs:
Once the blank terminal window is open, follow these steps to enter the number of battery packs:
•
Press ENTER to initiate terminal mode. Follow the prompts:
•
Press 1 to modify UPS Settings. Press e (or E) to modify the number of battery
packs. Enter the number of battery packs, including the internal battery pack
(Number of packs: 1= internal battery module,
2 = 1 external battery pack, 3 = 2 external battery packs, etc.).
Press ENTER.
•
Follow the prompts.
5. Exit the terminal program.
6. 1609-P5000E models only: Re-install the 1609-NMC network management card in the slot
located in the rear of the unit.