Rockwell Automation 937CS-AITMP-DC1 Universal Temperature Converter Installation Instructions User Manual
Page 21
20
Bul. 937
C Universal Temperature Converter Installation Instructions
Behavior of the current output of the Bul. 937CS-AITMP-DC1
The linear behaviour outside the measurement range described in the following only results if
temperature values ranging between the minimum value and the maximum value of the selected
sensor correspond to the current values. If this is not the case, the output current jumps to the
minimum or maximum specified value. The Diagnosis window (see
Diagnosis section) shows the message
Above limit or Below limit.
If you select Characteristic inverted, the conversion of start value and end value will be inverted.
Setting 4 mA ... 20 mA unlimited
At this setting, the start value of the measurement range is converted to 4 mA and the end value to
20 mA. Intermediate values are converted proportionately.
If the value falls below the start value, the output current decreases linearly to a minimum of 0 mA (-
25 % of the measurement range). Further decreases cannot be evaluated (output 0 mA). If the value
exceeds the end value, the output current increases linearly to a maximum of 22 mA (approx. 112.5 %
of the measurement range). Further increases cannot be evaluated (output approx. 22 mA).
Setting 4 mA ... 20 mA (NE 43)
≈ 22
20.0
0
0
100
≈ 112.5
-25
4.0
mA
% meas.
range
Start value
End value
20.5
20.0
0
0
100
≈ 103
-1.25
4.0
3.8
mA
% meas.
Start value
End value
range