All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

14

Rockwell Automation Publication 1606-RM014A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

17. Dielectric Strength

The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by
the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the
voltage with a slow ramp (2s up and 2s down). Connect all phase-terminals together as well as all output poles before
conducting the test. When testing, set the cut-off current settings to the value in the table below.

Fig. 17-1 Dielectric strength

A B C

Type test

60s

2500Vac

4000Vac

2000Vac

Factory test

5s

2500Vac

2500Vac

500Vac

Field test

5s

2000Vac

2000Vac

500Vac

Cut-off current setting

> 4mA

> 4mA

> 1mA

A

C

N

L

Input

Earth, PE

Output

-

+

B


To fulfill the PELV requirements according to EN 60204-1 § 6.4.1,
we recommend that either the + pole, the – pole or any other part
of the output circuit shall be connected to the protective earth
system. This helps to avoid situations in which a load starts
unexpectedly or can not be switched off when unnoticed earth
faults occur.