All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

16

Rockwell Automation Publication 1606-RM045A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

16. Protection Features

Output protection

Electronically protected against overload, no-load and short-circuits

*)

Output over-voltage protection

typ. 58Vdc
max. 60Vdc

In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.

Degree of protection

IP 20

EN/IEC 60529

Penetration protection

> 3.5mm

e.g. screws, small parts

Over-temperature protection

yes

Output shut-down with automatic restart

Input transient protection

MOV (Metal Oxide Varistor)

Internal input fuse

T6.3A H.B.C.

not user replaceable

*) In case of a protection event, audible noise may occur.

17. Safety Features

Input / output separation

*)

SELV

IEC/EN

60950-1

PELV

IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41

double or reinforced insulation

Class of protection

I

PE (Protective Earth) connection required

Isolation resistance

> 5MOhm

input to output, 500Vdc

PE resistance

< 0.1Ohm

Touch current (leakage current)

typ. 0.19mA / 0.44mA

100Vac, 50Hz, TN-,TT-mains / IT-mains

typ. 0.29mA / 0.65mA

120Vac, 60Hz, TN-,TT-mains / IT-mains

typ. 0.53mA / 1.04mA

230Vac, 50Hz, TN-,TT-mains / IT-mains

< 0.25mA / 0.54mA

110Vac, 50Hz, TN-,TT-mains / IT-mains

< 0.38mA / 0.79mA

132Vac, 60Hz, TN-,TT-mains / IT-mains

< 0.74mA /1.29mA

264Vac, 50Hz, TN-,TT-mains / IT-mains

*) double or reinforced insulation

18. Dielectric Strength

The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by
the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the
voltage with a slow ramp (2s up and 2s down). Connect all input terminals together as well as all output poles before
conducting the test. When testing, set the cut-off current settings to the value in the table below.

Fig. 18-1 Dielectric strength

A B C D

Type test

60s

2500Vac

3000Vac 500Vac 500Vac

Factory test

5s

2500Vac

2500Vac 500Vac 500Vac

Field test

5s

2000Vac

2000Vac

500Vac

500Vac

Cut-off current setting > 10mA

> 10mA

> 20mA

> 1mA

D

A

C

B

B

N

L

Input

DC-ok

Output

-

Earth, PE

+


To meet the PELV requirements according to EN60204-1 § 6.4.1, we
recommend that either the + pole, the – pole or any other part of
the output circuit be connected to the protective earth system.
This helps to avoid situations in which a load starts
unexpectedly or cannot be switched off when unnoticed earth
faults occur.