Rockwell Automation 802R Sealed Contact Limit Switches User Manual
Specifications, Lever positioning, Mounting
Installation and Operating Instructions
802R Sealed Contact Limit Switches
IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE.
General data
• Single contact sealed in glass envelope for high
reliability in contaminated atmospheres
• Programmable controller compatible at 24 volts and above
• 0.5 inch NPT conduit connection
• Lever type with spring return or maintained operation
• push type, wobble stick and cat whisker with spring
return operation
• Low operating torque (0.78 lb·in) lever type with spring
return requires 802T-W5 rod lever
• 802T-W6 micrometer adjustable roller lever provides
precise positioning with lever type models
The 802R sealed limit switches are available in several
configurations. Adhere to approved industry standard practices
and electrical codes when installing and wiring limit switches.
Contact Rockwell Automation support if clarification is needed.
Do not disconnect equipment while the
circuit is live unless the area is known to be
free of ignitable concentrations.
To avoid electrical shock and/or unintended
operation of equipment, disconnect all
power to the limit switch and the controlled
equipment before proceeding with any
repair or adjustment of the limit switch.
Handle with care. Contacts are
encapsulated in glass.
ATTENTION
IMPORTANT
19
(0.75)
12.7
(0.5)
6.35
(0.25)
14.73
(0.58)
21.34
(0.84)
7.11
(0.28)
16.76
(0.66)
0.5 in. Dia.
NPT
2--5.4 (0.213),
Dia. Holes for
Front Mtg.
29.46
(1.16)
38.86
(1.53)
38.1
(1.5)
59.44
(2.34)
72.14
(2.84)
55.63
(2.22)
45.21
(1.78)
45.21
(1.78)
Standard switch with 802T-W1 Lever
Specifications
AC contact rating
(maximum per pole, 50 or 60 Hz, same polarity)
DC contact rating
(maximum per pole, same polarity)
Lever positioning
The lever on rotary actuated
devices is adjustable to any
position through 360° around the
shaft. Loosen the nut, move lever
to desired position, and securely
retighten the nut (see figure).
Mounting
Position the conduit entering the switch so that any fluid
inside the conduit will not drain into the switch enclosure.
Apply sealing compound to conduit threads to prevent
entrance of fluid through the threads.
Certifications
UL listed and CSA certified
Suitable for use in Class I, Division 2, Groups A, B, C, and D,
and Class II, Division 2, Groups F and G.
Enclosure rating
NEMA 13
Ambient t emperature
[°C (°F)]
(Non-explosive
environments)
-29…+121 (-20…+250)
Exception:
Wobble stick and cat whisker devices are rated for
-18…+54 (0°…+130).
NEMA rating
designation
Max
voltage
A
Continuous
carrying
current
V A
Make
Break
Make
Break
B600
120
30
3.00
5
3600
360
240
15
1.50
5
3600
360
480
7.5
0.75
5
3600
360
600
6
0.60
5
3600
360
NEMA Rating
Voltage Range
Current Rating
P300
115…125V
230…250V
1.1 A
0.55 A
Do not energize the 802R limit switch in
explosive environments above 40°C (due to
potential ignition). The 802R has UL/CSA
temperature code of T6 at 40°C (104°F).
After wiring has been completed, check all
wiring screws for tightness.