Fault LED indications for
Bulletin 283A ArmorStart
Distributed Motor Controllers
Table 6
Controller Fault LED Definitions
Blink
Pattern
Definitions
Possible Causes or Remedies
1
Short Circuit
The motor circuit protector has tripped, or the internal wiring protection algorithm has detected an unsafe
current range. Try to reset the protector if tripped. If the condition continues, check the power wiring. This
fault cannot be disabled.
2
Overload trip
The load has drawn excessive current and based on the trip class selected, the device has tripped. Verify
that the load is operating correctly and the ArmorStart is properly set-up. This fault cannot be disabled.
3
Phase Loss
The ArmorStart has detected a missing phase. Verify that three-phase voltage is present at the line side
connections. This fault can be disabled and is disabled by default.
4
Shorted SCR
Prior to every start, the unit will check all SCRs for shorts and unit load connections to the motor. If there is
a shorted SCR in the SMC-3 and/or open load, the start will be aborted and a shorted SCR/open load fault
will be indicated. This prevents damage from phase imbalance. This fault cannot be disabled.
5
Phase Rotation
When enabled, 3-phase input power will be verified before starting. If input power phasing is detected to
be incorrect, the start will be aborted and a fault indicated. This fault can be disabled and is disabled by
default.
6
Control Power
The ArmorStart has detected a loss of the control power voltage. Check control voltage, wiring, and proper
polarity. Also check and replace the control voltage fuse, if necessary. This fault can be disabled and is
disabled by default.
7
I/O Fault
This error indicates a blown output fuse.
8
Over Temperature
This fault is generated when the operating temperature has been exceeded. This fault cannot be disabled.
9
Phase Imbalance
The ArmorStart has detected a voltage imbalance. Check the power system and correct if necessary. This
fault can be disabled and is disabled by default.
10
Reserved
Not Used
11
Internal Communication
This fault occurs when communication between the main board and the SMC-3 is lost. This fault cannot be
disabled.
12
Heatsink Over
temperature/JAM
This fault indicates either an over temperature fault or a JAM fault. The heatsink is monitored by
thermistors and the SCR temperature is tracked by an algorithm. When a maximum temperature is reached
by either, the microcomputer switches off the SMC and indicates a fault code of 12. A fault code of 12
could also indicate a JAM fault. This fault cannot be disabled.
13
EEPROM Fault
This is a major fault, which renders the ArmorStart inoperable. Possible causes of this fault are transients
induced during EEprom storage routines. If the fault was, initiated by a transient, power cycling should
clear the problem otherwise replacement of the ArmorStart may be required. This fault cannot be disabled.
14
Hardware Fault
This fault indicates that a serious hardware problem exists. Check for a base/starter module mismatch. If
no mismatch exists, the ArmorStart may need to be replaced. (Hdw Flt is the factory-enabled default
setting.) This fault cannot be disabled.
16
Miscellaneous Fault
This fault cannot be disabled.