1) Remove and lockout power sources feeding the unit.
2) Turn unit disconnect switch to the “OFF” position.

3) Remove all of the quick connect cables from the Control Module.
4) Loosen the four mounting screws on the Control Module.
5) Unplug the Control Module from the Base Module by slowly pulling straight forward.

WARNING

To prevent electrical shock, disconnect from power source before installing or servicing.

WARNING

The drive contains high voltage capacitors which take time to discharge after removal of main supply. Before working on drive, ensure

isolation of main supply from line inputs (R, S, T [L1, L2, L3]). Wait three minutes for capacitors to discharge to safe voltage levels. Failure

to do so may result in personal injury or death. Darkened display LEDs are not an indication that capacitors have discharged to safe voltage

levels.

Removal of Control Module

*The removal of the Base Module is only required for Base Module Replacement. If only the Control Module is being replaced, skip to Step 18.

6) Remove communications, input, and output cables from the Base Module.
7) Loosen the four mounting screws on the
Terminal Access Cover Plate.
8) Remove cover plate.
9) Loosen terminal screws.
10) Remove all wires from terminal
block.
11) Remove conduit fittings.

Removal of Base Module

With Conduit / Cable

With ArmorConnect Media

Motor

Cable

Terminal Access

Cover Plate

6

1

3

7

8

9

10

5

4

2

Control

Module

CAUTION

Verify that power is removed to motor, inputs, and outputs before replacing any module.

Control

Module

Base

Module

Disconnect SM

wire connection

between Control and

Base Modules

6) Remove communications, input and output cables from the Base
Module.
7) Remove the ArmorConnect Media from the gland plate by
loosening the fastner and un-plugging.

Skip to Step 12.

12) Loosen unit mounting screws and remove the Base Module.

12

3-Phase

Control

Voltage

-Bulletin 284D shown-

When Safety Monitor option used, there

is a wire connection between the Control

and Base Module that needs to be

disconnected.

Base
Module