Rockwell Automation 150-SM3_SM4 SMC-50 Soft Starter I/O Option Module Installation User Manual
Page 3
PN-164120
DIR 10000152878 (Version 01)
Publication 150-IN052B-EN-E
Specification
Type of Output
Electromagnetic Relay Contact
Number of Contacts
1
Type of Contact
Programmable: Normally Open (N.O.) or
Normally Closed (N.C.)
Rated Operational Current (Inductive)
3A @ 120V AC, 1.5A @ 240V AC
Rated Operational Current (Resistive)
8A @ 250V AC, 5A @ 30V DC
Rated Thermal Current (Ith)
5A (AC)
Max. Make / Break
3600VA Make, 360VA Break
UL Utilization Ratings
AC-15, B300 (AC Pilot Duty: NEMA)
Output Delay Time (max)
On-to-Off: 25 mS; Off-to-On 30 mS
Relay Life (electrical-Inductive Load
cos ø = 0.4)
250,000 operations
(3A @ 120V AC, 1.5A @ 240V AC)
Relay Life (mechanical)
10 million operations
150-SM4 Input and Output Specifications
Field Wiring Terminal Identification
A9
In
COM
NC
120 / 240V AC
NOTE: For control wiring
details refer to the SMC-50
User Manual
Inputs
InA1 InA2 InA3 InA4
AuxA1
AuxA2
AuxA3
Relay Outputs
A11 A12
L1
A1
A2
A3
A4
A5
A6
A7
A8
L1
L1
L1
L2
L2
L2
L2
A10
UL/CSA/NEMA
IEC
Nominal Operating Voltage
Operating Voltage Range
120/240V AC
85 to 264V AC @ 47 to 63 Hz
9.7 mA @ 47 Hz, 9.7 mA @ 62.4 Hz
On-state Current, Minimum
On-state Voltage, Minimum
Off-state Current, Maximum
Off-state Voltage, Maximum
74.5V AC @ 47 Hz, 55.9V AC @ 62.4 Hz
68.8V AC @ 47 Hz, 53.6V AC @ 62.4 Hz
9.0 mA @ 47 Hz, 9.3 mA @ 62.4 Hz
3.64 A
On-to-Off: 30 mS, Off-to-On: 25 mS
Inrush Current Max
Input Delay Time
Rated Insulation Voltage
Rated Impulse Voltage
Dielectric Withstand
Control Circuit:
150-SM4
Optional Inputs:
Terminals A1 and A2
NA 240V
NA
3000V
1600V AC
2000V
UL/CSA/NEMA
IEC
Nominal Operating Voltage
Operating Voltage Range
120/240V AC
85 to 264V AC @ 47 to 63 Hz
5.1 mA @ 47 Hz, 5.0 mA @ 62.4 Hz
On-state Current, Minimum
On-state Voltage, Minimum
Off-state Current, Maximum
Off-state Voltage, Maximum
74.5V AC @ 47 Hz, 55.8V AC @ 62.4 Hz
68.6V AC @ 47 Hz, 53.5V AC @ 62.4 Hz
4.7 mA @ 47 Hz, 4.8 mA @ 62.4 Hz
3.64 A
On-to-Off: 30 mS, Off-to-On: 25 mS
Inrush Current Max
Input Delay Time (Maximum)
Rated Insulation Voltage
Rated Impulse Voltage
Dielectric Withstand
Control Circuit:
150-SM4
Optional Inputs:
Terminals A3 and A4
(1)
Control Circuit:
150-SM4
Optional Outputs:
Terminals A6 thru A11
NA 240V
NA
3000V
1600V AC
2000V
(1) Meets IEC Type 2 specification per IEC 60947-1 for 240V AC only
NOTE: For additional information refer to the SMC-50 User manual (150-UM011x-EN-P) available from www.ab.com - Publications Library - Literature Library
(3)