beautypg.com

Rockwell Automation 802PR Type LA and Type XA, Series C Installation Instructions User Manual

Page 2

background image

802PR-IN002A-EN-P

77050-001-01

July 2013

Printed in Dominican Republic

PROGRAMMABLE OUTPUT SELECTION — The programmable
N.O./N.C. proximity switch is factory preset in either the normally
open or normally closed output mode.

To change the switch output mode use the following instructions.

1. Remove the lower legend plate on the front of the switch.
2. A line on the recessed rocker indicates the output mode of

the switch.

3. To change the output, depress the recessed rocker of the

switch with a pointed tool.

Note: Do not use a tool whose point could break and jam the
switch.

4. Replace the lower legend plate.

To return the output mode to its original setting, simply reverse
the above procedure. The OUTPUT LED will be ON when the
switch output is conducting.

HARD WIRED CONTACTS — When hard wired contacts are
connected in parallel with the Bulletin 802PR, a surge suppressor
MUST BE connected in parallel with the load. Surge suppression is
not required when hard wired contacts are connected in series
with the load. For recommended surge suppressors for various
devices, refer to publication 802PR-2.1 product data.

NOTE: Hard wired contacts that are operating in series or parallel
with the Bulletin 802PR Type LA or Type XA will cause a delay of
approximately 200 ms. This power-up delay will reduce the
maximum number of operations per minute and may result in a
momentary de-energization of the load.

CONDUIT COUPLED SWITCHES — Threaded conduit opening
bases are suitable for use with flexible conduit. Conduit coupler
bases are suitable for use with both flexible conduit and rigid
conduit. Both bases connect to 1/2 in.-14 NPT threaded conduit.
Switches with a “S6” suffix in their catalog number are suitable
for connection to ISO 20-1.5 threaded conduit.

PREWIRED CABLE SWITCHES — These switches include a
prewired cable for connection directly into a junction box. The
cable is a two conductor, oil resistant thermoplastic (STO).

PREWIRED RECEPTACLE SWITCHES — These switches include
a prewired receptacle suitable for use with the connector-cable
assemblies listed in the table below. Figure 6 indicates which two
pins of the receptacle are wired internally to terminals 1 and 2.
The third pin is not used.

Figure 6: End view of prewired receptacle

Connector Cable (supplied by user)

Manufacturer

Connector Cable Part Numbers

3-ft cable

6-ft cable

12-ft cable

Standard Color Code (green, black, white)

Brad Harrison

40901

40902

40903

Joy

X8984-3

8984-4

8984-5

CAM-LOK

E2057-624

E2057-625

E2057-626

Automotive Color Code (green, red, red)

Brad Harrison

40958

40959

40960

Joy

X8984-13

X8984-14

X8984-15

CAM-LOK

E2057-824

E2057-825

E2057-826

ATTENTION

Do NOT connect two or more Bulletin 802PR
switches in parallel. Erratic operation may

result.

Normally

closed

mode

Depress recessed rocker near

indicating line to change output mode

Normally

open

mode

Short Pin —
Connects to Terminal 1

Short Pin —
Connects to Terminal 2

Long Pin — Not used

TROUBLESHOOTING GUIDE — The following guide provides basic troubleshooting information for installation and use of the proximity
switch. If a problem occurs, attempt to determine the POSSIBLE CAUSE as listed. Apply the suggested SOLUTION.

NOTE: The switch may continue to operate even if the LED (will not light) is damaged.

 Programmable N.O./N.C. switches have two LEDs. The POWER LED will be ON when power is applied.
 N/A — Not Applicable.

MOUNTING DIMENSIONS — Dimensions shown in mm (inches).

Symptom

Output LED

Possible Cause

Solution

N.O.

N.C.

Load will not
energize

OFF

OFF

A. Power supply off.

A. Apply power.

OFF

ON

B. Incorrect voltage applied

B. Apply correct voltage.

OFF

OFF

C. Broken wires or loose connections.

C. Repair wiring or tighten loose connections.

OFF

ON

D. Improper wiring.

D. Recheck connection diagrams. Rewire

accordingly.

OFF

N/A 

E. Target too small or out of sensing range.

E. Increase target size of move target or switch

within sensing range.

N/A 

OFF

F. Target or metal object within sensing range. F. Remove target or metal object. Refer to

EFFECTS OF NEARBY METAL SURFACES.

OFF

OFF

G. Two or more proximity switches placed too

close together.

G. Move sensing faces of switches apart. Refer

to SPACING BETWEEN SWITCHES.

ON

ON

H. Load device faulty or incorrect.

H. Replace load or size load correctly.

Load will not
de-energize

ON

N/A 

A. Target or metal object within sensing range. A. Remove target or metal object. Refer to

EFFECTS OF NEARBY METAL SURFACES.

N/A 

ON

B. Target too small or out of sensing range.

B. Increase target size of move target or switch

within sensing range.

ON

ON

C. Two or more proximity switches placed too

close together.

C. Move sensing faces of switches apart. Refer

to SPACING BETWEEN SWITCHES.

ON

OFF

D. Improper wiring.

D. Recheck connection diagrams. Rewire

accordingly.

OFF

OFF

E. Load device faulty or incorrect.

E. Replace load or size load correctly.

Load energizes and
de-engerizes
intermittently

ON & OFF intermittently

A. Broken wires or loose connections.

A. Repair wiring or tighten loose connections.

B. Target fluctuates in and out of sensing

range and hysteresis zone.

B. Stabilize target within the sensing range.

Refer to SPECIFICATIONS — Hysteresis.

C. Two or more proximity switches placed too

close together.

C. Move sensing faces of switches apart. Refer

to SPACING BETWEEN SWITCHES.

www.rockwellautomation.com

Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fas: (852) 2508 1846

Power, Control and Information Solutions Headquarters

41

(1-5/8)

26

(1-1/84)

109

(4-11/32) 117

(4-5/8)

42

(1-21/32)

6 (15/84)
dia. holes

Front mounting

US (1-5/32 x 2-11/32)

DIN (30 x 60)

6 (15/84)

41

(1-5/8)

1/2 in.-14 NPT

Inside threads

Threaded Conduit Opening

15

(19/32)

(1-5/32)

(2-11/32)

Rear mounting hole pattern

front view

2 #10-32 tapped holes

9.5 (3/8) deep

30

(1-5/32)

60

(2-11/32)

Front mounting hole pattern

front view

2 holes for #10 or M5 screws

22

(13/16)

7/8 in.-16N

outside threads

Prewired cable

1 in. hub

1/2 in.-14 NPT

inside threads

15

(19/32)

Conduit Coupler

10 (13/32) dia.

16 AWG

2 conductor

STO cable

Prewired receptacle

16

(5/8)

 Type LA only.

 Also available with ISO 20-1.5 threads.